Installation manual

8 Operating manual ecoCRAFT
4.4 Operator field with multi-function display
1
Fig. 4.3 Display in normal operation
The ecoCRAFT units are fitted with a digital information
and analysis system. This system provides information
on the operating status of your appliance and helps you
deal with problems.
In the ready for operation mode and in burner operation,
the display shows a single figure operating code. This
indicates the current operating condition of the boiler
and the current temperature at the feed manifold, e.g.:
"3 45" = Burner in heating operating mode "3",
forward flow temperature "45 °C"
Operational displays
The operational display provides information on the
operational condition of your unit. The operation codes
1, 2 and 5 appear at the start of each individual module.
The number of the individual module is preset on the
operational display.
The following displays occur under normal operating
conditions:
Operation
code
Description of functions
0 Standby, no heating function
1 The fan on the relevant module starts up and
prevents the burner chamber
2 Ignition is active, the burner ignites
3 The burner burns in heating mode
4 The burner burns in hot water mode
5 The air pressure monitor responds
6 Regulator switch-off of the burner in heating
mode
7 Pump overrun, heating pump
8 Pump overrun, charging pump hot water cylinder
9 Regulator switch-off of the burner in hot water
mode
Table 4.1 Operation codes
In the event of a fault, the fault signal flashes alternately
with the basic display (see Chapter 5).
4 Operation