For the installer Instructions for installation and servicing ecoTEC Wall hung room sealed fan assisted condensing boiler ecoTEC plus 612 ecoTEC plus 615 ecoTEC plus 618 ecoTEC plus 624 ecoTEC plus 630 ecoTEC plus 637 ecoTEC plus 824 ecoTEC plus 831 ecoTEC plus 837 ecoTEC pro 28 ecoTEC pro 24 GB
Contents Contents 1 1.1 1.1.1 1.1.2 1.1.3 1.2 1.3 1.4 1.5 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . Notes on the documentation . . . . . . . . . . . . . . . . Applicable documents . . . . . . . . . . . . . . . . . . . . . . Retention of documents . . . . . . . . . . . . . . . . . . . . Safety instructions and symbols . . . . . . . . . . . . . Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents 7 7.1 7.1.1 7.1.2 7.1.3 Inspection and maintenance . . . . . . . . . . . . Initial inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview of the inspection and maintenance tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1.4 Functional check of boiler operation . . . . . . . . . 7.
1 Introduction 1 Introduction 1.2 1.1 Notes on the documentation The following information is intended to help you throughout the entire documentation. Further documents apply in combination with this installation and maintenance manual. We assume no liability for any damage caused by non-observance of these manuals. 1.1.
Introduction 1 increase the flexibility. If desired, an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions. All boilers have a built in diagnostic system which indicates the operational status of the boiler. This feature provides key information to aid commissioning and fault finding. The data badge is fitted to the underside of the boiler. See text of General Requirements for installation requirements or notes.
2 Boiler specifications 2 Boiler specifications 2.1 Technical data Technical data CH heat output range 80 °C flow/60 °C return 60 °C flow/40 °C return 50 °C flow/30 °C return 40 °C flow/30 °C return Maximum DHW output 824 ecoTEC plus 831 837 ecoTEC pro 24 28 6.7 – 19.0 6.9 – 19.6 7.1 – 20.2 7.2 – 20.6 8.7 – 24.0 9.0 – 24.7 9.2 – 25.5 9.4 – 26.0 12.0 – 28.0 12.3 – 28.9 12.7 – 29.7 12.9 – 30.3 6.7 – 19.0 6.9 – 19.6 7.1 – 20.2 7.2 – 20.6 9.0 – 24.0 9.3 – 24.7 9.6 – 25.5 9.8 – 26.
Boiler specifications 2 ecoTEC plus Technical data CH heat output range 80 °C flow/60 °C return 60 °C flow/40 °C return 50 °C flow/30 °C return 40 °C flow/30 °C return Category SEDBUK Band SAP Seasonal Efficiency Inlet gas working pressure required (G20, natural gas) Inlet gas working pressure required (G31, Propane) Connected load (if needed, related to stored charge/water heating) at 15 °C and 1013 mbar Exhaust mass rate at minimum thermal load (40 °C flow/30 °C return at maximum thermal load (80 °C flow
2 Boiler specifications 2.2 Dimensions 9 65 8 190 440 175 241 7 6 642 720 883 125 10 11 12 20 5 4 3 2 1 35 100 45 300 75 130 180 ecoTEC plus 630: 334 ecoTEC plus 637, ecoTEC plus 837: 368 35 100 5 4 3 2 1 Fig. 2.
Boiler specifications 2 2.4 Installation 14 14 1 13 1 2 2 3 13 4 3 4 5 5 12 6 12 11 10 10 7 8 9 Fig. 2.2 Function elements of combination boilers Legend: 1 Expansion vessel 2 Air intake pipe 3 Burner module 4 Ignition electrode 5 Fan 6 Diverter valve with by-pass 7 Pump 8 Aqua-Sensor 9 Electronics box 10 Pressure sensor 11 Hot water heat exchanger 12 Gas valve 13 Heat exchanger 14 Flue pipe connection 7 9 Fig. 2.
3 General requirements 3 General requirements 3.1 Preliminary remarks for room sealed appliances This appliance should only be installed in conjunction with either a Vaillant flue system or an alternative approved system (details of flue approval categories can be found in the technical section of the installation manual). Install the flue system as detailed in the separate flue installation instructions supplied with this boiler. 3.
General requirements 3 1 8 1 8 2 7 2 7 3 6 4 5 3 6 4 5 Fig. 3.1 Contents included with delivery of ecoTEC plus system boilers Fig. 3.2 Contents included with delivery of ecoTEC plus combination boilers DO NOT remove the boiler from the polystyrene base at this stage. DO NOT remove the boiler from the polystyrene base at this stage.
3 General requirements 1 7 2 6 i F 3.4 Installation site The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also provide adequate space for servicing and air circulation around the boiler.
General requirements 3 10 Flue pipe Danger! Vaillant appliances are certified only for use with genuine Vaillant flue pipes. Only use genuine Vaillant flue pipes. Malfunctions can occur if you use other accessories. These may result in damage and injury. You will find a list of genuine flue pipes in the Vaillant installation manual for flue pipes. The CE mark is valid only if the appliance is operated with Vaillant flue pipes. 40 1435 880 3.6 550 3.
3 General requirements 3.7 Flue termination The following details refer to both flue systems. a. The terminal must be located where the combustible substances can escape freely at all times. b. A plume of water vapour will sometimes be visible from the flue terminal. Positions where this could be a nuisance should be avoided. c.
General requirements 3 3.9 Electrical supply A 230 V, ~ 50 Hz single phase electricity supply fused to 3 Amp. must be provided in accordance with the latest edition of BS 7671 (IEE Wiring Regulations) and any other local regulations that may apply. In IE reference should be made to the current edition of the ETCI rules. The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary controls.
Vessel Volume [L] Initial system pressure (bar) 1.0 Pressure relief valve setting (bar) 1.5 3.0 Total water content of system litres 25 50 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 For system volumes other than those given above, multiply the system volume by the factor across 2.7 5.4 10.9 13.6 16.3 19.1 21.8 24.5 27.2 30.0 32.7 35.7 38.1 40.9 43.6 46.3 49.0 51.8 54.5 3.9 7.8 15.6 19.5 23.4 27.3 31.2 35.1 39.0 42.9 46.8 50.7 54.6 58.5 62.4 66.3 70.2 74.1 78.0 0.109 0.
Boiler installation sequence 4 safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co-ordinated movements during lift. Always use assistance if required. Carriage of carton from point of delivery to point of installation – ground floor. Recommend 2 person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck.
4 Boiler installation sequence min 5 165/246* Required minimum distances/assembly clearances min 5 min 500** min 180 Positioning of Appliance for Final Installation – in roof space restricting installation. This appliance is deemed to be a one person lift when removed from the carton. Obtain firm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to drop into place onto bracket.
Boiler installation sequence 4 Note Care should be taken not to scratch the white surface of the boiler casing. 20 165 4.2.3 Using boiler template • Fix the paper template to the wall ensure that the template is vertical. 175 95 5 The template shows: – The position of the fixing holes for the boiler mounting bracket. – The position of the connections. – The position of the flue exit hole. 60/100 5 25 • Mark the position of the hanging bracket fixing holes.
4 Boiler installation sequence 4.3 Flue exit • If using rear flue mark the position of the air/flue duct and its circumference. Note Lift the boiler from either side at the bottom edge Other flue options Flue instructions for other flue systems such as vertical RSF flues, flues run to the side of the boiler and the use of additional bends etc. are detailed in the flue installation instructions provided with the boiler.
Boiler installation sequence 4 4.9 Gas connection Note With the spacer frame (Art. No 308 650), the pipes can be fitted vertically upwards behind the appliance. The distance of the appliance from the wall thus increases by 65 mm. Danger! The gas connection may only be made by a competent person. The legal directives and the local regulations for gas supply companies must be observed. • Fit the union nut (6) and the compression olive (5) to the pre-formed tail provided with ecoTEC plus appliances (7).
4 Boiler installation sequence 4.11 Condensate drain pipe bar 1 2 7 4 a 6 d c b 6 1 2 3 Internal stackpipe 3 Internal discharge system 5 7 Gulley Soakaway 3 4 5 Fig. 4.7 Installing the hot and cold water connection (ecoTEC pro combination boiler) Note Flush all foreign matter from the mains supply before connecting to the boiler. • Insert the seal (1) and connect the service valve (2) to the appliance cold water connection.
Boiler installation sequence 4 b)connecting into the internal discharge branch (e.g. sink waste or washing machine) with an external termination, the condensate discharge pipe should have a minimum diameter of 22 mm with no length restriction and should incorporate a trap with a 75 mm (3) (built into the boiler) seal. The connection should preferably be made down stream of the sink waste trap. If the connection is only possible upstream, then an air break is needed between the two traps.
4 Boiler installation sequence Caution! To ensure fumes do not escape through the syphon of the boiler the trap must be filled with water before the boiler is turned on. Therefore the discharge pipework should be installed so as not to interfere with the removal and refitting of the condensate trap, we recommend the outlet pressure release valve pipe supplied is not shortened. You must leave a bottom clearance of at least 180 mm below the condensate trap for removal and refitting.
Boiler installation sequence 4 Danger! This appliance must be earthed. • Feed the power supply flex into the appliance and the control panel through the cable clamps provided and tighten. Danger! Mains connection terminals L and N remain live even when the boiler on/off control is switched off. Note Do not connect any power voltage to the connections 7-8-9 or BUS (+,-). - + 7 89 L N 3 45 Note Ensure that all cords pass through the cable clamps in the rear of the control box and are securely fixed.
4 Boiler installation sequence 4.14.3 Electric board layout eBUS accessory connection Burner cable harness Accessory module connection Diagnosis via eBUS, vrnetDIALOG outer probe ext.
Boiler installation sequence 4 NTC return NTC flow Ignition electrode X 20/5 red X 20/7 black X 20/8 blue X 20/7 black X 20/13 black Thermal fuse X 20/12 black Gas valve assembly Fan unit Plug in coupling X 20/16 blue (earth) X 20/4 grey (PWM) X 20/3 black (Hall signal) X 20/18 red (24 VDC) X 20/17 red (24 VDC) X 20/9 blue (earth) X 2/16 black A X 2/7 pink B X 2/15 brown C Water pressure sensor X 2/8 blue D Diverter valve X 2/9 black X 2/11 red X 2/12 green Pump Aqua sensor X 2/4 orange X 2/3
4 Boiler installation sequence NTC return NTC flow Ignition electrode X 20/5 red X 20/7 black X 20/8 blue X 20/7 black X 20/13 black Thermal fuse X 20/12 black Fan unit Gas valve assembly Plug in coupling X 20/16 blue (earth) X 20/4 grey (PWM) X 20/3 black (Hall signal) X 20/18 red (24 VDC) X 20/17 red (24 VDC) X 20/9 blue (earth) X 2/10 black Hot water contact C1/C2 X 2/14 brown Pump Water pressure sensor X 2/9 black X 2/11 red X 2/12 green X 2/4 orange tank NTC connection X 2/10 black X2
Boiler installation sequence 4 4.15 Controls 4.15.1 Vaillant controls and accessories Controller Item no.
4 Boiler installation sequence 5 Commissioning Part I the room containing the room thermostat should not be fitted with a TRV). 4.17 Frost protection The boiler has an integral frost thermostat which is designed for protection of the boiler. To protect remote or exposed parts of the heating system or property additional frost protection measures must be taken such as the installation of an external frost thermostat.
Commissioning Part I 5 5.4.1 Checking the filling pressure of the heating system 4 plus pro 3 i F P bar 1 2 2 1 bar Fig. 5.2 Filling device ecoTEC plus combination boiler Fig. 5.1 Checking the filling pressure of the heating system Note The ecoTEC appliances come with a manometer and a digital pressure indicator. The manometer allows you to quickly check whether the filling pressure is in target range or not even when the appliance is turned off.
5 Commissioning Part I 5.4.3 Filling the heating system in ecoTEC pro combination boilers and ecoTEC plus system boilers The ecoTEC pro combination boilers and the ecoTEC plus system boilers do not come with a filling device. In these appliances, water is filled in the heating system through a filling pipe provided onsite. • Join a hose between a cold water dispensing valve and the filling pipe of the heating system. • To fill, first open the cold water dispensing valve.
Commissioning Part I 5 5.7 Adjusting the pumping capacity 5.9 Checking the gas supply Only in ecoTEC plus boilers: The capacity of the two-stage pump can be adjusted to the requirements of the heating system. If needed, change the setting of the operating mode dependent pump speed under the diagnostic number “d.19” (see section 8.1.2). 5.9.1 Factory settings 5.8 Adjusting the by-pass The appliances have an adjustable by-pass valve. The pressure can be adjusted between 170 and 350 mbar. Approx.
5 Commissioning Part I Natural gas: DO NOT proceed with adjustment or attempt to put the unit into service if the inlet working pressure lies outside the 17–25 mbar range. 5.10 Refitting the case 2 LPG: DO NOT proceed with adjustment or attempt to put the unit into service if the inlet working pressure is lower than 37 mbar. 1 • Turn off the appliance, remove U gauge. • Tighten the test point screw and check for leaks.
Commissioning Part I 5 Functional checks (commissioning part II) 6 5.11 Adjusting the central heating output (range rating) The boilers are fully modulating for central heating, and it is therefore not necessary to range rate the boiler. However, if desired, it is possible to range rate the boiler, as follows: • Press the “i” and “+” buttons simultaneously. • Keep the “+” button pressed until “d.0” is displayed. Note The display runs from “d.0” to “d.99” before restarting at “d.0”. • Press the “i” button.
6 Functional checks (commissioning part II) 6.1.2 Heating • Switch on the appliance. • Make sure that there is a heating demand. • Press “i” to activate the status indicator. As soon as a heat demand is received, the appliance runs through the status indicators “S. 1” to “S. 3”, until the appliance is running correctly in normal mode and the display shows “S. 4”. plus pro Fig. 6.2 Display indicator during heating mode 6.1.3 Water heating (combination boilers only) • Switch on the appliance.
Functional checks (commissioning part II) 6 Inspection and maintenance 7 with the heat input (kW) and temperature difference between flow and return. • Leave the user instructions and the installation instructions with the user. 6.3 Vaillant warranty Vaillant provide a full parts and labour warranty for this appliance. The appliance must be installed by a suitably competent person in accordance with the Gas Safety (Installation and Use) Regulations 1998, and the manufacturer’s instructions.
7 Inspection and maintenance 7.1.2 Maintenance Before commencing any servicing or maintenance work, carry out an initial inspection of the system as follows: • Inspect the flue, pipework and electrical connections for indications of damage or deterioration. • Inspect the air supply and ventilation arrangements of the installation. • Check the heating and water system, in particular the condition of radiator valves, evidence of leakage from the heating system and dripping hot water taps. 7.1.
Inspection and maintenance 7 7.2 Servicing the burner module Caution! Damage to corrugated gas pipe! Under no circumstances must the burner module be suspended from the flexible corrugated gas pipe. 7.2.1 Removing the burner module The burner module consists of the burner, fan, gas valve und the gas supply (mixer tube). These four components make up the complete assembly, the burner module. Danger! There is danger of being injured or burnt by the burner module and at all components carrying water.
7 Inspection and maintenance • Check the burner surface for damage, replace the burner if necessary. • After checking/replacing the burner, re-assemble the burner module in the boiler as described in Section 7.2.4. 1 7.2.4 Refitting the burner module 1 2 3 4 Fig. 7.5 Replacing the burner door seal • Insert a new seal (1) in the burner door. Fig. 7.
Inspection and maintenance 7 • Tighten the four nuts (4) on the alternate left and right sides until the burner door fits closely and uniformly to the stop surfaces. • Reconnect the HT lead (5) and earth lead (6) to the spark electrode. • Insert the cables (8) on the fan motor and the cable (7) on the gas fitting. 7.3 Cleaning the condensate siphon 1 2 1 Fig. 7.9 Cleaning the condensate siphon 3 Fig. 7.
7 Inspection and maintenance 8 Troubleshooting 7.4 Checking the expansion vessel • Fill out the Benchmark gas boiler commissioning checklist at the rear of this guide. 1 Fig. 7.10 Checking expansion vessel admission pressure Fig. 7.11 Function check Note It is not necessary to perform this check every year – a check every three years is sufficient. • • • • Ensure the boiler CH service valves are closed. Release the pressure from the boiler. Remove valve cap from expansion vessel charge point.
Troubleshooting 8 8.1.1 Status codes The status codes that you can see on the display provides information about the current operating condition of the appliance. The display of the status codes can be called as follows: plus pro Display Meaning Warm start (ecoTEC combination boilers only) / Charge hot water cylinder (ecoTEC system boilers only): S.20 Warmstart demand S.21 Fan running S.22 Pump running S.23 Ignition sequence S.24 Burner ignited S.25 Fan and water pump running S.26 Fan over run S.
8 Troubleshooting First Diagnostic level • Press the “i” and “+” keys simultaneously. The display shows “d.0”. • Use the “+” or “–” keys to scroll through the desired diagnostic numbers of the first diagnostic level (see table 8.2). • Press the “i” key. You can end the diagnostic mode as follows: • Press the “i” and “+” keys simultaneously. or • Do not press any key for approx. 4 minutes. The current heating flow temperature appears in the display again.
Troubleshooting 8 Second diagnostic level • As described above in the first diagnostic level, scroll through the diagnostic number d.97. • Change the displayed value to 17 (password) and press the “i” button. You are now in the second diagnostic level where all information from the first diagnostic level (see table 8.2) and the second diagnostic level (see table 8.3) is displayed. Display Meaning d.17 d.18 d.
8 Troubleshooting Display Meaning d.78 Display value/adjustable value Storage charging temperature limit (target flow temperature in storage mode, system boilers only) Heating operating hours Adjustment range in °C 55 to 90 (Factory setting: 80) in h1) d.
Troubleshooting 8 Code Meaning Cause F.25 Interruption in the compact thermal module cable harness Incorrect sensing of flame Compact thermal module cable harness defective F.27 F.28 Flame detector defective F.
8 Troubleshooting 9 Parts replacement 8.4 Test programs Special functions can be triggered on the appliances by activating various test programs. These programs are given in detail in the Table 8.5. • The test programs P.0 to P.6 will be started when “Power ON” is turned on and the “+” key is pressed for 5 s. The display shows “P.0”. • Press the “+” key to start counting the test number upwards. • Press the “i” to operate the appliance now and to start the test program.
Parts replacement 9 • Remove the three screws (2) on the burner module (1). • Remove the complete “gas valve/fan” unit. 5 1 Fig. 9.1 Replacing burner • Loosen the 4 screws (1) on burner, and remove the burner. • Mount the new burner with a new seal. Ensuring that the notch in the burner aligns with the burner viewing window. • Install the burner module as described in Section 7.2.4. • After completing the work, check for gas leaks and perform a function check (see section 7.6)! 9.
9 Parts replacement 9.5 Replacing primary heat exchanger Danger! Before replacing the component, comply with the safety instructions in Section 9.1. 1 2 • Disconnect the appliance from the mains as described in Section 9.1, and close the service valve in the gas supply pipe. • Close the flow and return service valves and drain the appliance. • Remove the burner module as described under 7.2.1. • Remove the expansion vessel as described under 9.4.
Parts replacement 9 9.6 Replacing electronics and display Danger! Before replacing the component, comply with the safety instructions in Section 9.1. 1 2 3 Fig. 9.6 Primary heat exchanger holder • Disconnect the plug-in connection (2) of the thermal fuse in the primary heat exchanger. • Remove the three screws (3) on the primary heat exchanger holder. • Turn the holder to the side around the rivet (1), pull the primary heat exchanger downwards to the right and remove it from the appliance.
9 Parts replacement 10 Recycling and disposal 11 Vaillant service Settings 1 Natural gas (H) Propane Tolerance Tolerance CO2 after 5 min. full load mode with appliance front closed CO2 after 5 min. full load mode with appliance front removed Set for Wobbe-Index W0 CO value with full load Unit 9.2 ± 1,0 10.2 ± 0,5 Vol.–% 9.0 ± 1,0 10.0 ± 0,5 Vol.–% 15 < 250 22.5 < 250 kWh/m3 ppm Table 9.
Appendix Appendix Instructions for installation and servicing ecoTEC 53
839592_05 GB 08 2006
834449_09GB_082006.qxd 10.08.
834449_09GB_082006.qxd 10.08.
834449_09GB_082006.qxd 10.08.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 4 CONTENTS: PART 1 CONCENTRIC 60/100 The air/flue duct must be installed by a suitably qualified service provider, which is responsible for observing the relevant specifications, regulations and standards.
10.08.2006 12:20 Seite 5 REQUIREMENTS Regulations and standards to be observed ☞ Vaillant ecoMAX/ecoTEC boilers are certified as heating boilers with corresponding flue systems according to EC Directive 90/396/EEC on gas-fired devices. This installation manual is covered by this certification and is referred to in the design approval test certificate. ☞ These instructions should be read in conjunction with the instructions for installation and servicing supplied with the boiler.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 6 PLANNING THE AIR/FLUE DUCT LAYOUT Alternative termination accessories available 303 933 = Horizontal air/flue duct 303 936 = Horizontal telescopic air/flue duct 303 900 = Vertical air/flue duct (black) Optional connection accessories 303 900 303 933 303 936 Accy. No.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 7 PLANNING THE AIR/FLUE DUCT LAYOUT PART 1 CONCENTRIC 60/100 Air/flue duct extension 470 mm Ø 60/100 Vaillant Accy. No.: 303 902 Air/flue duct extension 970 mm, Ø 60/100 Vaillant Accy. No.: 303 903 GU_LAZ 70/0 Air/flue duct extension 1970 mm, Ø 60/100 Vaillant Accy. No.: 303 905 Fig. 1.1: Extensions, Ø 60/100 Elbow, 87°, Ø 60/100 Vaillant Accy. No.: 303 910 27 27 18 27 18 18 Bends, 45° (pack of 2), Ø 60/100 Vaillant Accy. No.: 303 911 Fig. 1.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 8 PLANNING THE AIR/FLUE DUCT LAYOUT 250 Adjustable flue support clips, Ø 100 (pack of 3) Vaillant Accy. No.: 303 935 Fig. 1.5: Flue support clips, Ø 100 Telescopic extension (PP), Ø 60/100 440 mm - 690 mm Vaillant Accy. No.: 303 906 440 – 690 Fig. 1.6: Telescopic extension, Ø 60/100 33 – 56 Offset section, Ø 60/100 Vaillant Accy. No.: 303 919 Fig. 1.7: Offset section, Ø 60/100 303919_IAx 290 – 374 155 Sliding sleeve (PP), Ø 60/100 Vaillant Accy.
Seite 9 PLANNING THE AIR/FLUE DUCT LAYOUT 25 PART 1 CONCENTRIC 60/100 Adjustable roof tile for pitched roof Vaillant Accy. No.: 009 076 (black) 132 5 8 49 GU_LAZ 41/0 12:20 Fig. 1.9: Adjustable roof tile for pitched roof Flexible pitched roof seal (black) Vaillant Accy. No.: 303 980 132 495 10.08.2006 495 Fig. 1.10: Flexible pitched roof seal Flat roof penetration collar Vaillant Accy. No.: 009 056 130 153 834449_09GB_082006.qxd 390 Fig. 1.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 10 PLANNING THE AIR/FLUE DUCT LAYOUT Variable termination kit - black Vaillant Accy. No.: 303 942 For 303 933 and 303 936 only Variable termination kit - white Vaillant Accy. No.: 303 946 For 303 933 and 303 936 only Fig. 1.13: Variable termination kit Extension pipe for variable termination kit Ø 60 mm 1 m - black including 1 support clip Vaillant Accy. No.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 11 PLANNING THE AIR/FLUE DUCT LAYOUT 60 PART 1 CONCENTRIC 60/100 Flue support clip, Ø 60 mm delivered with kits Fig. 1.17: Flue support clip, Ø 60 mm Maximum flue lengths for use with ecoMAX ecoMAX Accessories 613/2 E 618/2 E 622/2 E 824/2 E 828/2 E 635/ E 835/ E pro 18 E pro 28 E 8.0 m incl. 1 elbow 87° 7.0 m incl. 1 elbow 87° 8.0 m incl. 1 elbow 87° 4.0 m incl. 1 elbow 87° 10.0 m incl. 1 elbow 87° Accy. No. Horizontal 303 933 Max.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 12 PLANNING THE AIR/FLUE DUCT LAYOUT Maximum flue lengths for use with ecoTEC ecoTEC Accessories Accy. No. Horizontal flue systems 303 933 Max. permitted concentric flue length Fig. 1.18 plus 612 plus 615 plus 618 plus 624 plus 824 plus 630 plus 831 plus 637 plus 837 pro 24 pro 28 plus plus plus plus 415 418 428 438 10.0 m 8.0 m 8.0 m 8.0 m 8.0 m 5.5 m incl. incl. incl. incl. incl. incl.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 13 Maximum flue length Fig. 1.19: Vertical flue systems Flue length outside Fig. 1.18: Horizontal flue systems LAS Euro B/S 074/0 LAS Euro B/S 074/0 Maximum flue length PART 1 CONCENTRIC 60/100 PLANNING THE AIR/FLUE DUCT LAYOUT Concentric flue length Fig. 1.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 14 INSTALLING THE AIR/FLUE DUCT SLIDING SLEEVE 3 5 Fig. 2.0: Installing the sliding sleeve 14 ☞ NOTE: For installations where there is insufficient movement to allow fitting of the flue into flue outlet, a sliding sleeve (Accy. No. 303 915) is available. When using the sliding sleeve both the air and flue ducts of the last extension must be shortened by a further 95 mm.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 15 INSTALLATION OF THE HORIZONTAL AIR/FLUE DUCT Horizontal air/flue duct 754 Accy No.: 303 933 (Length 0.75 m) 65 Contents of the accessory: • Horizontal air/flue duct • 87° elbow • 1 x 48 mm air duct clamp • 1 x 30 mm air duct clamp • Internal trim ring Ø 100 • External wall seal.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 16 INSTALLATION OF THE HORIZONTAL AIR/FLUE DUCT (TOP OUTLET) • Once the position of the flue exit hole has been determined, the hole should be cut through the wall using a core drill of 125 mm diameter. Note: If access can be gained to the proposed flue exit point from outside the dwelling, the hole can be cut with a 107 mm core drill and the flue external wall seal fitted from outside the dwelling.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 17 • Push the air/flue duct assembly (1) including the flexible external seal through the wall until the seal clears the outside face of the wall and pull air/flue duct back towards the boiler until the external seal touches the outside wall (fig. 3.8 and fig 3.12). 87 13 Fig. 3.12 LAS Euro B/S 001/0GB 1 • Ensure that the air/flue duct (1) is centred in the hole and the terminal is correctly positioned with the inlet grille at the bottom (fig 3.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 18 INSTALLATION OF THE TELESCOPIC HORIZONTAL AIR/FLUE DUCT IMPORTANT: The air/flue duct is not concentric and the air duct has a slope of 1.5° (if the air flue duct is not cut). The hole through the wall can therefore be drilled horizontally with no slope. Horizontal telescopic air/flue duct 405 - 610 Accy No.: 303 936 (Length 0.4 - 0.61 m) 48 65 Fig. 3.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 19 • Once the position of the flue exit hole has been determined, the hole should be cut through the wall using a core drill of 125 mm diameter. Note: If access can be gained to the proposed flue exit point from outside the dwelling, the hole can be cut with a 107 mm core drill and the flue external wall seal fitted from outside the dwelling. Fig. 3.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 20 INSTALLATION OF THE TELESCOPIC HORIZONTAL AIR/FLUE DUCT (TOP OUTLET) • Push the air/flue duct assembly (1) including the flexible external seal through the wall until the seal clears the outside face of the wall and pull air/flue duct back towards the boiler until the external seal touches the outside wall (fig. 3.14 and fig. 3.18). 87 13 Fig. 3.
10.08.2006 12:20 Seite 21 INSTALLATION OF THE BLACK TERMINAL KIT Black terminal kit Accy. No.: 303 934 Contents of the accessory: • Black terminal • External wall seal Fig. 3.19: Black kit Assembly Before installing the flue duct Fig. 3.20: Releasing the catches • Use an 8 mm screwdriver to bend the catches inwards (fig. 3.20). • Pull the terminal together with the flue duct out of the air duct (fig. 3.21).
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 22 INSTALLATION OF THE BLACK TERMINAL KIT Assembly After installing the flue duct Danger! Before starting work, shut down the appliance and prevent it from being switched on unintentionally. Fig. 3.23: Flue duct • Remove the wall seal from the terminal. • Use an 8 mm screwdriver to bend the catches inwards (fig. 3.20). • Pull the terminal together with the flue duct out of the air duct (fig. 3.21).
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 23 INSTALLATION OF THE VARIABLE TERMINATION KIT Important: The flue outlet of the variable termination must face directly upwards. PART 1 CONCENTRIC 60/100 Flue Terminal Clearances Minimum flue terminal clearances are defined in BS5440, and these must apply unless the boiler manufacturer has received approval to quote smaller clearances that are not safety critical.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 24 INSTALLATION OF THE VARIABLE TERMINATION KIT • Unlock the catch between the terminal and the flue duct by twisting them against each other (fig. 4.5). • Pull the terminal out of the flue duct. • Push the variable terminal onto the flue duct. ☞ Please note: The catch on the top of the variable terminal must lock firmly into the notch in the flue duct (fig. 4.6). Fig. 4.5: Unlocking the catch Caution! Make sure the seal fits tightly.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 25 • Fit the pipes and bends, working from the variable terminal to the selected location for the flue exit using support clips supplied fig 4.8, 4.9, 4.10 or 4.11. Caution! Pipe extensions must be fixed to the wall using pipe clamps. Use one clamp for each extension directly beside the sleeve. Fit another clamp to the extension after each 87° bend (fig. 4.9). Caution! The extension pipe expands when heated. Leave 1 cm expansion space in each sleeve.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 26 INSTALLATION OF THE VARIABLE TERMINATION KIT Fig. 4.10: Installation of basic kit with two additional 87° bends showing position of support clips Fig. 4.
4449_09GB_082006.qxd 10.08.2006 12:20 Seite 27 min 400 mm min 100 mm Routing around roof eaves When routing the variable termination kit around the roof eaves, additional lengths of M8 threaded bar will be required for the support brackets. Threaded bar can be purchased from most local merchants. • Change the bird protection grille from the 87° elbow to the extension installed at the end. ☞ If using the 87° elbow, use the seal from the pipe extension.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 28 INSTALLATION OF THE VERTICAL AIR/FLUE DUCT ☞ Observe the maximum flue lengths as detailed in table on page 11. Vertical air/flue duct Accy. No.: 303 900 (black) 40 880 1435 550 Contents of the accessory: • Vertical air/flue duct and terminal assembly • 40 mm air duct clamp • Fixing bracket ☞ See page 6 et seq. for details of air/flue duct elements. Fig. 5.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 29 INSTALLATION OF THE VERTICAL AIR/FLUE DUCT 550 5 20 885 –5 0 1 0-5 6 Ø100 8 2 750 4 100- 110 * 3 8 * = 190 mm ecoMAX combination and system boilers * = 176 mm ecoMAX pro and ecoTEC plus open vent * = 125 mm ecoTEC plus system & combination Fig. 5.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 30 INSTALLATION OF THE VERTICAL AIR/FLUE DUCT Flat-roof installation 550 5 cold roof warm roof 885 1 120 7 Fig. 5.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 31 FITTING AIR/FLUE DUCT EXTENSIONS Use a saw, tin-snips, etc. to cut tubes to size. ☞ No tools are required when separating extensions for cutting to size air and flue tubes separately. When doing so, the flue conduit should be twisted into a position where the shoulders on the plastic tube can be pushed through the spacer-piece. After cutting to size, refit the flue conduit and secure it to the air conduit.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 32 FITTING AIR/FLUE DUCT EXTENSIONS How to install 2x 87° elbows 2 1 Fig. 6.1: Arrangement of 2 x 87° elbows – View from above • When using elbows for long flue runs in a corner follow fig. 6.4 and fig. 6.5 to avoid obtrsuctions. ☞ Note: The elbows must be correctly aligned to avoid undue stress on the joints an risk of leakage.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 33 FITTING AIR/FLUE DUCT EXTENSIONS 90 ☞ Note: The elbows must be correctly aligned to avoid undue stress on the joints an risk of leakage. The elbow fitted to the top of the boiler (1) should be twisted by 3° to ensure that the second 87° elbow (2) exits the wall perpendicular. When using 87° elbow install with a slope of 3° between wall and air-flue pipe (fig. 6.4) or use 2 x 45° elbows (fig. 6.5). * 2 1 max. 5 m *=3 max. 5 m Fig. 6.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 34 FITTING AIR/FLUE DUCT EXTENSIONS How to install 87° elbows Accy. No.: 303 910 ☞ Note: The elbow delilvered with the flue kits 303 933 and 303 936 is not the same dimension as shown here. 1 90 Offset Example: Length of air conduit 95 An offset of 400 mm is measured. This value is then used, along with the table below, to determine the length of the air conduit ( = 190 mm in this case).
10.08.2006 12:20 Seite 35 FITTING AIR/FLUE DUCT EXTENSIONS How to install 45° elbows 10 Le ng th of a ir co nd ui t An offset of 400 mm is measured. This value is then used, along with the table below, to determine the length of the air conduit (= 284 mm) and the height (= 420 mm). Important: This gives a corresponding exhaust-conduit length of 284 + 40 = 324 mm. Fig. 6.4: Installation of 45° bends Table 6.
834449_09GB_082006.qxd 36 10.08.
834449_09GB_082006.qxd 10.08.
834449_09GB_082006.qxd ¤ 10.08.2006 12:20 Seite 38 REQUIREMENTS Regulations and standards to be observed ☞ Vaillant ecoMAX/ecoTEC boilers are certified as heating boilers with corresponding flue systems according to EC Directive 90/396/EEC on gas-fired devices. This installation manual is covered by this certification and is referred to in the design approval test certificate.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 39 PLANNING THE AIR/FLUE DUCT LAYOUT Alternative termination accessories available 303 200 = Vertical air/flue duct (black) 303 209 = Horizontal air/flue duct 303 926 = Appliance connection piece 303 200 303 209 Accy. No.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 40 PLANNING THE AIR/FLUE DUCT LAYOUT 18 58 25 Appliance connection piece Ø 80/125 Vaillant Accy. No.: 303 926 (with 2 measuring apertures) Fig. 1.1: Appliance connection piece Air/flue duct extension (PPs) 470 mm, Ø 80/125 Vaillant Accy. No.: 303 202 Air/flue duct extension (PPs) 970 mm, Ø 80/125 Vaillant Accy. No.: 303 203 GU_LAZ 70/0 Air/flue duct extension (PPs) 1970 mm, Ø 80/125 Vaillant Accy. No.: 303 205 Fig. 1.
Seite 41 PLANNING THE AIR/FLUE DUCT LAYOUT Sliding sleeve (PPs), Ø 80/125 Vaillant Accy. No.: 303 215 164 GU_LAZ 76/0 120 Fig. 1.5: Sliding sleeve, Ø 80/125 Adjustable roof tiles for pitched roof Vaillant Accy. No.: 009 076 (black) 132 5 PART 2 CONCENTRIC 80/125 25 8 GU_LAZ 41/0 49 Fig. 1.6: Adjustable roof tile for pitched roof Flexible pitched roof seal (black) Vaillant Accy. No.: 303 980 132 495 12:20 495 Fig. 1.7: Flexible pitched roof seal Flat roof penetration collar Vaillant Accy.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 42 PLANNING THE AIR/FLUE DUCT LAYOUT Maximum flue lengths for use with ecoMAX ecoMAX Accessories Accy. No. Horizontal flue systems 303 209 Max. permitted concentric flue length 613/2 E 618/2 E 622/2 E pro 18 E pro 28 E 13.0 m incl. 1 elbow 87° 25.0 m incl. 1 elbow 87° 30.0 m incl. 1 elbow 87° 20.0 m incl. 1 elbow 87° Maximum length of flue is reduced by 2.5 m for each additional 90° elbow. Maximum length of flue is reduced by 1.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 43 PLANNING THE AIR/FLUE DUCT LAYOUT Maximum flue lengths for use with ecoTEC ecoTEC Accessories Accy. No. 303 209 Max. permitted Horizontal concentric flue systems flue length plus plus plus plus plus plus 612 plus 615 13.0 m incl. 1 elbow 87° 618 624 630 824 831 25.0 m incl. 1 elbow 87° Maximum length of flue is reduced by 2.5 m for each additional 90° elbow. 303 200 Max. permitted Vertical concentric flue systems flue length 14.0 m 27.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 44 PLANNING THE AIR/FLUE DUCT LAYOUT LAS Euro B/S 074/0 Maximum flue length Fig. 1.10 44 LAS Euro B/S 074/0 Maximum flue length Fig. 1.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 45 CHANGING THE APPLIANCE CONNECTION-PIECE Installation Accy No.: 303 926 2 1 The appliance is supplied ready-fitted with the connection-piece for the 60/100 air/flue duct system. • Loosen the four screws (2) and pull the appliance connectionpiece (1) upwards to remove it. • Refit the fixing screws (2). Fig. 2.0: Fitting the appliance connection-piece The seals are sensitive to mineral oil-based grease products.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 46 INSTALLATION OF THE SLIDING SLEEVE 3 5 Fig. 3.0: Installing the sliding sleeve 46 ☞ NOTE: For installations where there is insufficient movement to allow fitting of the flue into flue outlet, a sliding sleeve (Accy. No. 303 215) is available. When using the sliding sleeve both the air and flue ducts of the last extension must be shortened by a further 85 mm.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 47 ☞ Observe the maximum flue lengths as detailed in table on page 42. 1103 70 70 15 IMPORTANT: The air/flue duct is not concentric and the air duct has a slope of 1.5° (if the air flue duct is not cut). The hole through the wall can therefore be drilled horizontally with no slope. Horizontal air/flue duct Vaillant Accy No.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 48 INSTALLATION OF THE HORIZONTAL AIR/FLUE DUCT Ø 80/125 WITH EXTENSIONS IMPORTANT: The air/flue duct is not concentric and the air duct has a slope of 1.5° (if the air flue duct is not cut). The hole through the wall can therefore be drilled horizontally with no slope. Where extensions are used, these must be installed with a slope at 3° ± 1° (equivalent to 50 mm ± 20 mm rise per metre length) to ensure that condensate dows not remain in the sleeve.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 49 A Fig. 4.5 Mark air duct here 10 mm LAS Euro B/S 084/0 Dimension A + 20 Dimension 60 mm mm Fig. 4.6 15 mm 25 mm Fig. 4.7 LAS Euro B/S 080/0 Mark flue duct here • Taking each extension to be used, fit the flue duct into the air duct and secure using the 3 screws provided. • For ease of measuring and marking the air/flue duct extensions, assemble them loosely together with the air/flue duct and terminal assembly as shown (fig. 4.6).
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 50 INSTALLATION OF THE HORIZONTAL AIR/FLUE DUCT Ø 80/125 WITH EXTENSIONS 220 3 15 Fig. 4.8: Installing the horizontal wall duct 50 LGU_LAZ 384/0_IT 1 • Push the assembled air/flue duct and terminal assembly through the flue exit hole until it protrudes 220 mm out from the outside wall. • Ensure that the terminal is correctly positioned with the air inlet grille at the bottom.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 51 INSTALLATION OF THE HORIZONTAL AIR/FLUE DUCT (80/125 Ø) Indirect installation • Fit the wall mounting (2). 6 • Install the appliance (3) with reference to the installation and servicing instructions supplied with the boiler. 253 4 ** 82 - 90 • Join the 87° elbow to the appliance connection piece.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 52 INSTALLATION OF THE VERTICAL AIR/FLUE DUCT Vertical air/flue duct Accy. No.: 303 200 (black) Contents of the accessory: • Vertical air/flue duct and terminal assembly • Adapter (air) for Ø 110/125 • 70 mm air duct clamp • Fixing bracket Fig. 5.1: Vertical roof duct GU_LAZ 81/0 880 70 1530 650 ☞ Observe the maximum flue lengths as detailed in table on page 42. ☞ See page 41 et seq. for details of air/flue duct elements.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 53 INSTALLATION OF THE VERTICAL AIR/FLUE DUCT 790 5 740 20 –5 0 1 0-5 6 Ø125 8 2 82 - 90 4 750 * 3 8 750 mm ecoMAX combination and system boilers 530 mm ecoMAX pro and ecoTEC plus open vent (top holes of bracket) 622 mm ecoTEC plus system & combination 7 * = 190 mm ecoMAX combination and system boilers * = 176 mm ecoMAX pro and ecoTEC plus open vent * = 125 mm ecoTEC plus system & combination Fig. 5.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 54 INSTALLATION OF THE VERTICAL AIR/FLUE DUCT Flat-roof installation 650 5 cold roof warm roof 880 1 120 6 2 7 Fig. 5.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 55 FITTING AIR/FLUE DUCT EXTENSIONS How to add extensions Use a saw, tin-snips, etc. to cut tubes to size. L air 1. 2 25 2. 1 15 + 40 mm Fig. 6.1: Cutting tubes to size ☞ The seals are sensitive to mineral oil-based grease products. For this reason, the seals must not be greased. If the seals need wetting to aid in installation, use water only.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 56 FITTING AIR/FLUE DUCT EXTENSIONS How to install 2x 87° elbows 2 1 Fig. 6.1: Arrangement of 2 x 87° elbows – View from above 2 1 * *=3 Fig. 6.2: Arrangement of 2 x 87° elbows – View from front 2 1 * *=3 Fig. 6.3: Arrangement of 2 x 87° elbows – View from side 56 • When using 2 x 87° elbows follow fig. 6.1 to fig. 6.3 to avoid obstructions on outer wall.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 57 FITTING AIR/FLUE DUCT EXTENSIONS max. 5 m • When using elbows for long flue runs in a corner follow fig. 6.4 and fig. 6.5 to avoid obtrsuctions. 90 ☞ Note: The elbows must be correctly aligned to avoid undue stress on the joints an risk of leakage. The elbow fitted to the top of the boiler (1) should be twisted by 3° to ensure that the second 87° elbow (2) exits the wall perpendicular.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 58 FITTING AIR/FLUE DUCT EXTENSIONS How to install 87° elbows Accy. No.: 303 210 Example: Length of air conduit 95 Important: This gives a corresponding exhaust-conduit length of 190 + 40 = 230 mm. 10 95 10 GU_LAZ 102/2GB An offset of 400 mm is measured. This value is then used, along with the table below, to determine the length of the air conduit (= 190 mm in this case). 1 90 Offset Fig. 6.3: Installation of 90° elbows Table 6.
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 59 FITTING AIR/FLUE DUCT EXTENSIONS How to install 45° elbows Height Accy. No.: 303 211 Example: 10 Le ng th of a ir co nd ui t An offset of 400 mm is measured. This value is then used, along with the table below, to determine the length of the air conduit (= 284 mm) and the height (= 420 mm). 10 Offset GU_LAZ 103/2GB Important: This gives a corresponding exhaust-conduit length of 284 + 40 = 324 mm. Fig. 6.
834449_09GB_082006.qxd 60 10.08.
834449_09GB_082006.qxd 10.08.
834449_09GB_082006.qxd 62 10.08.
834449_09GB_082006.qxd 10.08.
10.08.2006 12:20 Seite 64 834449_09 GB 082006 834449_09GB_082006.
Spare part catalogue 0020010870.
Content General view of sheet ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Page 3 04 Burner Page 4 06 Heat exchanger Page 6 07 Casing parts Page 8 08 Connection parts (Hydroblock) Page 10 08a Connection parts Page 14 08b Connection parts (Acc.
2 0020010870.
General view of sheet ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 02-00-077 Subject to alteration ! Attention: Please take the gross price from the valid price list ! 3
04 Burner ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 4 0020010870.
04 Burner ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.
06 Heat exchanger ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 6 0020010870.
06 Heat exchanger ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.
07 Casing parts ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 8 0020010870.
07 Casing parts ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.-No 01 180932 Part 02-07-073 flue adapter 60/100 02 147392 cap (set of 5) 03 981232 packingring 04 981233 packingring 05 180935 covering, cpl. VUW 246/3-5, with parts 06, 07, 08, 09, 10, 11 05 180935 covering, cpl. VUW 246/3-5 R1, with parts 06, 07, 08, 09, 10, 11 05 180935 covering, cpl. VUW 316/3-5, with parts 06, 07, 08, 09, 10, 11 05 180935 covering, cpl.
08 Connection parts (Hydroblock) ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 10 0020010870.
08 Connection parts (Hydroblock) ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.
08 Connection parts (Hydroblock) ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 12 0020010870.
08 Connection parts (Hydroblock) ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.
08a Connection parts ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 14 0020010870.
08a Connection parts ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.-No 01 180946 Part 02-08-120 connection tube, cpl. 02 193537 packingring (set of 10) 03 103415 packingring (set of 10) 04 103417 clip (set of 10) 05 178992 clip (set of 10) 06 180948 connection tube, cpl. 07 193539 packingring (set of 10) 08 180949 connection tube, cpl.
08b Connection parts (Acc.) ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 16 0020010870.
08b Connection parts (Acc.) ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.-No 01 082782 Part 02-08-125 gas shut-off valve, cpl. 01 082782 gas shut-off valve, cpl. VUW 246/3-5 R1 01 082782 gas shut-off valve, cpl. VUW 316/3-5 01 082782 gas shut-off valve, cpl. VUW 316/3-5 R1 01 082794 gas shut-off valve, cpl.
12 Control box ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 18 0020010870.
12 Control box ecoTEC plus 824 VUW 246/3-5 + R1 ecoTEC plus 831 VUW 316/3-5 + R1 ecoTEC plus 837 VUW 376/3-5 R1 Pos. Art.-No Part 02-12-046 01 193582 casing, cpl. 02 251955 fuse 2.0 AT (set of 10) 03 117319 knobs, cpl. grey (3 knobs) 04 0020028736 printed circuit board 05 117321 display 06 180982 pressure gauge Type, note 2.
20 0020010870.
General view of sheet ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 02-00-077 Subject to alteration ! Attention: Please take the gross price from the valid price list ! 21
04 Burner ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 22 0020010870.
04 Burner ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.
04 Burner ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 24 0020010870.
04 Burner ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.-No 20 193597 Part 02-04-038 screw, cpl. (set of 10) 21 0020025929 sealing gasket 22 193599 air inlet duct, cpl. VU 126/3-5, with part 23 22 193599 air inlet duct, cpl. VU 126/3-5 R1, with part 23 22 193599 air inlet duct, cpl.
06 Heat exchanger ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 26 0020010870.
06 Heat exchanger ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.
07 Casing parts ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 28 0020010870.
07 Casing parts ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.-No 01 180932 Part 02-07-073 flue adapter 60/100 02 147392 cap (set of 5) 03 981232 packingring 04 981233 packingring 05 180935 covering, cpl. VU 126/3-5, with parts 06, 07, 08, 09, 10, 11 05 180935 covering, cpl.
08 Connection parts (Hydroblock) ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 30 0020010870.
08 Connection parts (Hydroblock) ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.-No Part 02-08-121 Type, note 01 509142 support 02 178969 packingring (set of 10) 03 193535 packingring (set of 10) 04 178967 screw, cpl. (set of 10) 05 509143 connection piece,cpl.
08 Connection parts (Hydroblock) ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 32 0020010870.
08 Connection parts (Hydroblock) ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.
08a Connection parts ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 34 0020010870.
08a Connection parts ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.-No 01 180946 Part 02-08-120 connection tube, cpl. 01 180946 connection tube, cpl. VU 126/3-5 R1, with parts 02, 03 01 180946 connection tube, cpl. VU 156/3-5, with parts 02, 03 01 180946 connection tube, cpl.
08b Connection parts (Acc.) ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 36 0020010870.
08b Connection parts (Acc.) ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.-No 01 082782 Part 02-08-125 gas shut-off valve, cpl. 01 082782 gas shut-off valve, cpl. VU 126/3-5 R1 01 082782 gas shut-off valve, cpl. VU 156/3-5 01 082782 gas shut-off valve, cpl. VU 156/3-5 R1 01 082782 gas shut-off valve, cpl.
12 Control box ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 38 0020010870.
12 Control box ecoTEC plus 612 VU 126/3-5 + R1, ecoTEC plus 615 VU 156/3-5 + R1 ecoTEC plus 618 VU 186/3-5 + R1, ecoTEC plus 624 VU 246/3-5 + R1 ecoTEC plus 630 VU 306/3-5 + R1, ecoTEC plus 637 VU 376/3-5 R1 Pos. Art.-No Part 02-12-046 01 193582 casing, cpl. 02 251955 fuse 2.0 AT (set of 10) 03 117319 knobs, cpl. grey (3 knobs) 04 0020028736 printed circuit board 05 117321 display 06 180982 pressure gauge Type, note 2.
Notes 40 0020010870.
0020010870.
For the owner Instructions for use ecoTEC Wall hung room sealed fan assisted condensing boilers ecoTEC plus 612 ecoTEC plus 615 ecoTEC plus 618 ecoTEC plus 624 ecoTEC plus 630 ecoTEC plus 637 ecoTEC plus 824 ecoTEC plus 831 ecoTEC plus 837 ecoTEC pro 24 ecoTEC pro 28 GB
Contents Appliance characteristics Contents Appliance characteristics Appliance characteristics . . . . . . . . . . . . . . . . . . . . . 2 1 1.1 1.2 1.3 1.4 Notes on these instructions . . . . . . . . . . . . . . Storage of the documents . . . . . . . . . . . . . . . . . . . Symbols used in this manual . . . . . . . . . . . . . . . . . CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data badge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 3 3 3 2 2.
Notes on the documentation 1 Safety 2 1 Notes on these instructions To ensure clarity of information in instructions a new European standard of advice and symbols is being introduced. To ensure compliance with this new standard the following details are included. The following information is intended to help you throughout the boilers entire instruction pack. We assume no liability for any damage caused by non-observance of these instructions.
2 Safety 2.3 Safety instructions Always observe the following safety instructions and regulations. Danger Inflammable mixtures of gas and air may explode. Do not use or store explosive or easily flammable substances such as petrol or paint in the same room as the appliance. Danger Risk of poisoning and explosion due to a malfunction. Never put the safety devices out of operation or tamper with them so as to impair their function. 2.
Instructions on operation 3 3 Instructions on operation 3.1 Factory guarantee 3.1.1 Two 2 year guarantee for ecoTEC plus appliances Vaillant undertakes to rectify any manufacturing defect that occurs within twenty-four months of the installation date. For the 2nd year of the guarantee to be valid an annual service must be carried out by a CORGI registered installer one year after installation. The cost of this annual service is not included in the guarantee. 3.1.
4 Operation 4 Operation 4.1 Overview of controls on ecoTEC plus Advanced multifunctional display system 1 1 10 2 9 i i F F P P 3 bar bar 4 8 7 6 5 Fig. 4.2 Display on ecoTEC plus Fig. 4.1 ecoTEC plus controls For access to the controls open the front flap by pulling at the centre of the case strip.
Operation 4 Hot water supply active (ecoTEC plus combination boilers only) Illuminated: Hot water demand 10 Maximum radiator temperature control 11 Maximum hot water temperature control and warmstart ON/OFF (ecoTEC system boilers only) Illuminated: Heating of an indirect hot water cylinder turned on Flashing: Heating demand from the hot water cylinder, burner on Multifunctional display system ecoTEC pro boiler has a multifunction display (1).
4 Operation 4.3 • On ecoTEC combination boilers only: Ensure the cold water service valve (2) is open. This can be checked by opening a hot water tap and ensuring water flows. Initial checks before turning on 4.3.1 Opening the service valves Note If a bottom cover is fitted to the boiler the service valves are behind this cover. Caution The pressure relief valve is provided for safety reasons and must not be interfered with. 2 4.3.
Operation 4 Note Your appliance has a pressure sensor. If the pressure falls below 0.6 bar the pressure flashes in the display. If it falls below 0.3 bar the appliance switches off. The error message F.22 appears in the display. The system must be filled with water before you start up the appliance again. 4.5 Domestic hot water with ecoTEC combination boilers The boiler must only be used when the heating system contains water (see 4.3.2). 4.5.1 Setting the water temperature plus 4.
4 Operation 4.5.2 Switching the warmstart function on and off The warmstart system of the ecoTEC combination boilers provides you with hot water at the required temperature immediately. To do this, the hot water heat exchanger of the ecoTEC is kept at a pre-selected temperature level and the boiler will therefore periodically operate to maintain this temperature. ecoTEC pro: 1 b a ecoTEC plus: 2 1 b b a c 1 b c 1 Fig. 4.
Operation 4 4.6 Heating operation 4.6.2 Switching off heating (summer operation) The boiler must only be used when the heating system contains water (see 4.3.2). plus pro 4.6.1 Setting the maximum radiator temperature control plus pro i F P 2 1 1 bar i F Fig. 4.14 Switching off heating (summer operation) P bar You can switch off the heating in summer without switching off the hot water supply. • Turn the knob (1) for setting the maximum radiator temperature all the way to the left. 4.6.
4 Operation The boiler will now operate automatically to provide central heating for the conditions selected on the external controls (ecoTEC combination boilers will also provide domestic hot water on demand). After the boiler stops operating the pump will continue to operate for a short period to fully disperse the heat from the boiler.
Operation 4 4.8.1 Problems due to low system water pressure The device switches to “Fault” if the water pressure in the heating system is too low. This malfunction is indicated by the fault code “F.22” (dry fire) or “F.23” or “F.24” (lack of water). You can only start up the appliance again when the heating system is sufficiently filled with water. 4.9 Turning off the boiler i F P 4.8.2 Ignition problems plus 1 pro bar 2 1 Fig. 4.
4 Operation 4.10 Frost protection The frost protection feature only protects the boiler. Any other parts of the system liable to frost damage should be protected accordingly. Caution The frost protection and monitoring systems are only active when the main ON/OFF control of the appliance is in the “I” position and it is not disconnected from the main power supply. Frost protection function The boiler has a frost protection function.
Instructions for use ecoTEC 15
16 Instructions for use ecoTEC
bar +5 C +20 C +15 C +20 C i P VRT/VRC F
Instructions for use ecoTEC 19
838402_04 GB 08 2006