Technical data

Flue gas installation
26 Installation and maintenance instructions ecoTEC plus 0020116700_06
7
7.2 Flue termination
The following details refer to all flue systems.
a. The terminal must be positioned such that the prod-
ucts of combustion can disperse freely at all times.
b. A plume of water vapour will sometimes be visible
from the flue terminal. Positions where this could be a
nuisance should be avoided.
c. If the terminal is fitted less than 2m above a balcony,
above ground or above a flat roof to which people
have access then a suitable terminal guard must be
provided and fitted (contact Tower Flue Components,
Tonbridge, TN9 1TB).
i
Vertical flues must not terminate within 600mm
of an openable window, air vent or any other
ventilation terminal.
The flue system shall be so placed or shielded as to prevent
ignition or damage to any part of the building.