Technical data
Adapting the boiler to the heating installation
52 Installation and maintenance instructions ecoTEC plus 0020116700_06
11
Code Parameter Adjustable values
Factory
setting
Your own
setting
D.091 Status DCF with external sensor con-
nected
No reception
Reception
Synchronised
Valid
Not adjustable
D.093 Setting of device specific number (DSN) Setting range: 0 to 99
D.094 Delete fault history Delete fault list
D.095 Software version of PeBUS components PCB (BMU)
Display(AI)
actoSTOR(APC)
HBI/VR34
Not adjustable
D.096 Factory setting Reset all adjustable parameters to factory setting
D.098 Value of coding resistors for gas group
and output range
Display xx.yy
xx = Coding resistor 1 in cable harness for output
range:
08 = VU 612, VU 615, VU 618, VUW 824
09 = VU 624, VUW 831
10 = VU 630
11 = VU 637, VUW 837
yy = Coding resistor 2 on PCB for gas group:
02 = P-Gas
03 = H-Gas
Not adjustable
11.1 Diagnosis codes (continued)
11.1.1 Setting the heating partial load
The heating partial load of the Vaillant ecoTEC plus boiler is
factory set to "auto". This means that the boiler independ-
ently determines the optimum heating output depending on
the current heat demand of the system. A setting is nor-
mally no longer required. If you still want to set a fixed
maximum heating partial load, you can set a value under
diagnosis code "D.000", which equates to the boiler output
in kW.
11.1.2 Setting pump overrun time and pump
operating mode
The pump overrun time for the heating mode is set at the
factory to a value of 5 minutes. You can set the pump over-
run time under diagnosis code "D.001" within the range of
1minute to 60 minutes. You can set a different pump oper-
ating mode under diagnosis code "D.018". Here you have
the choice between Eco and Comfort.
Comfort (continuously operating pump)
The internal pump is switched on when the heating flow
temperature is not at "Heating off"(¬Operating instruc-
tions) and the heating requirement is enabled via an exter-
nal controller.