Owner's manual

Table Of Contents
User's Guide _______________________________________________________________________
38 ___________________________________________________________________ M210762EN-G
5. Lock the probe in place by tightening the locking screws on the
bar.
0604-024
Figure 22 Installing the Probe through Process Wall
0604-025
Figure 23 Installing Probe through Thick Walls
120
cooling bar
sealing material
(for example,
mineral wool)
PROCESS
(t
max
= 350 °C)
mounting flange
to be
welded
cooling
sleeve
ø89.5 + 0.5
DRYCAP
®
sensor
O-ring FPM
protective
tube
channel with
mineral wool
125
(max. 175 mm)
PROBE
cooling
fins
locking screws
of the probe
M4×6 DIN 916
(AISI 316)
marking
hole
8
40.6
to be welded
ø89.5 + 0.5
lengthening
piece
inner plate of the
process wall
wall thickness
< 160
plate ring plate pipe
the flange is fixed
with screws or by
spot welding
cooling
profile
~45º
ø118
NOTE:
Make sure that
the cooling profile
does not cover the
locking screws