Owner manual

User's Guide _______________________________________________________________________
20 ___________________________________________________________________ M211659EN-B
DIP Switches of Analog Output Models
1402-027
Figure 6 DIP Switch Settings of Analog Output Models
DIP
Position
Setting
1
Non-metric
Non-metric units (°F).
Metric
Metric units (°C).
2
Td
Td (dewpoint) as humidity parameter on display and
analog output. Sets analog output scaling
to -20 ... +55 °C.
RH
RH (relative humidity) as humidity parameter on display
and analog output. Sets analog output scaling to
0 ... 100 %RH.
3
0...5V or
0...20 mA
Set analog output channels to 0 ... 5 V (voltage output) or
0 ... 20 mA (current output)
0...10V or
4...20 mA
Set analog output channels to 0 ... 10 V (voltage output)
or 4 ... 20 mA (current output)
4
Not used
5
Not used
6
Not used
7
Not used
8
Custom
Configuration through service port only.
DIP
Configuration by DIP switches only.
Resets display analog outputs to standard settings.
NOTE
If DIP switch 8 is set to Custom, the transmitter ignores all other DIP
switch settings. In custom mode the transmitter uses settings that are
configured in software using the service port. Before changing the
position of this switch, see section Changing Between DIP and Custom
Configuration on page 21.
Non-Metric
Td
0...20mA
Custom
Metric
RH
4..20mA
DIP
1
2 3 4
5 6
7
8
Non-Metric
Td
Custom
Metric
RH
DIP
1
2 3 4
5 6
7
8
GMW93 GMW94
0...5V
0...10V