Owner manual
User's Guide _______________________________________________________________________
22 ___________________________________________________________________ M211659EN-B
DIP Switches of Digital Output Models
1209-016
Figure 7 DIP Switch Settings of Digital Output Models
DIP
Position
Setting
1
Modbus
Modbus protocol in use.
BACnet
BACnet protocol in use.
2 ... 4
A
B
C
Serial line baud rate.
Off
Off
Off
Automatic (default).
Off
Off
On
4800 (not available with BACnet protocol)
Off
On
Off
9600
Off
On
On
19200
On
Off
Off
38400
On
Off
On
57600
On
On
Off
76800
On
On
On
115200
5
Parity Even
Select 8 data bits, parity even, one stop bit
(8E1) for Modbus protocol.
Parity None
Select 8 data bits, parity none, and two stop bits
(8N2) for Modbus protocol.
6
Non-Metric
Use non-metric units on display and service
port. No effect on Modbus and BACnet.
Metric
Use metric units on display and service port.
No effect on Modbus and BACnet.
7
Not used
8
Not used
NOTE
If the serial line baud rate is set to Automatic, the transmitter attempts to
determine the baud rate of the traffic in the RS-485 network. The
transmitter cycles through all baud rate choices, listening for 10 seconds
at each rate. When it detects valid RS-485 traffic, it remains at the
detected baud rate until it is reset or power cycled.
1
ON
2 3 4
5 6
7
8
Modbus
BACnet
Parity Even
A B C
Parity None
Baud
Rate
1
2 3 4
5 6
7
8
128 64 32 16 8 4 2 1
Address
(Binary Weighting)
ON
Metric
Non-Metric