Wiring GMW95
The RS-485 line of the transmitter is isolated from the power supply. A
separate ground reference terminal (GND) is provided for the RS-485
connection.
If you are using a shielded cable, you can use the Shld terminal to hold
the exposed part of the shield. Note that the Shld terminal is floating
(not electrically connected).
1209-014
Figure 18 Wiring GMW95
Connecting Several Transmitters on Same RS-485
Line
Set the RS-485 termination jumper to “ON” on the transmitter that is at
the end of the line. This terminates the line with a 120 Ω resistor. For
location of the jumper, see Figure 4 on page 17.
Connect the cable shield to ground on the building controller side.
1209-015
Figure 19 Several Transmitters on Same RS-485 Line