Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles 
VAISALA _______________________________________________________________________ 47 
indication is given with the single character P or F. This is followed by 
the description of the measured parameter, which is followed by the 
actual measured value. 
The Bad 1 second readings counter is a running total of the number of 
fundamental 1-second readings that the sensor flagged as bad. This 
number rolls over to zero after reaching the count value of 65535. It is 
initialized to zero on each power-up or any other activity that performs a 
re-initialization of the sensor. The time measurement quality indices are 
given for path numbers as follows: 
-  Path 0 is from south transducer to north transducer 
-  Path 1 is from north transducer to south transducer 
-  Path 2 is from north transducer to east transducer 
-  Path 3 is from east transducer to north transducer 
-  Path 4 is from east transducer to south transducer 
-  Path 5 is from south transducer to east transducer 
A listing for the command response is given below with representative 
values. 
<CR><LF> 
P Heater voltage 22.3 Volts <CR><LF> 
P Array heater resistance 4.9 Ohms <CR><LF> 
P Heaters off voltage 0.1 Volts <CR><LF> 
P Incoming supply voltage 12.2 Volts <CR><LF> 
P 5.0 volt supply 5.05 Volts <CR><LF> 
P 10 volt supply 10.2 Volts CR LF 
- Bad 1 second reading counter 0 <CR><LF> 
P Path 0 signal quality index 99 <CR><LF> 
P Path 1 signal quality index 99 <CR><LF> 
P Path 2 signal quality index 99 <CR><LF> 
P Path 3 signal quality index 99 <CR><LF> 
P Path 4 signal quality index 99 <CR><LF> 
P Path 5 signal quality index 99 <CR><LF> 
The test limits for the various tests are as listed below: 
-  Heater voltage good in range 18.0 to 26.0 V 
-  Array heater resistance good in range 4.0 to 6.0 Ω 
-  Heaters off voltage good if below 0.5 V 
-  Incoming supply voltage good in range 10.5 to 13.5 V 
-  5.0 V supply good in range 4.5 to 5.5 V 
-  10 V supply good in range 9.0 to 11.0 V 
-  Signal Quality Index good above 50 