Owner`s manual
26
43” (1093 mm) to underside of combustible cavity
* 55-1/2” (1410 mm) with 12” vent pipe
* 45” (1143 mm)
37” (940 mm)
Required
clearance
to vertical
pipe is
within
stand-off
space
12” pipe section
14-1/2”
(369 mm)
Stand-off
9-3/8”
(238 mm)
19-1/4”
(489 mm)
Fireplace
* 58” (1473 mm) with 12” vent pipe
* 47-1/2” (1207 mm)
36-1/2” (927 mm)
2-1/2”
(64 mm)
14-1/2”
(369 mm)
9-3/8”
(238 mm)
19-1/4”
(489 mm)
Fireplace
12” pipe section
*Notes—ALL venting considerations
• Dimensions of venting are based on
using Dura-Vent elbows. Elbow curve
radius dimensions will vary when using
other brands and in general are slightly
bigger.
• Minimum 12 inches vertical pipe section
required within vent system either right
off unit or downstream after horizontal
run. Refer to venting chart on page 29 for
allowable horizontal runs.
• 3 inches to combustibles required above
horizontal pipe. Slope pipe upwards 1/4
inch per foot. 1 inch clearance required
around sides and bottom of horizontal
pipe and around vertical pipe.
• When calculating effective pipe lengths
subtract approximately 1-1/2 inch for
pipe joint - for example, a 12 inches pipe
section will add approximately 10-1/2
inches overall.
Venting Considerations—Vertical Takeoff
Venting Considerations—Horizontal Takeoff
Framing Requirements