43” (1093 mm) to underside of combustible cavity
* 55-1/2” (1410 mm) with 12” vent pipe
* 45” (1143 mm)
37” (940 mm)
Required
clearance
to vertical
pipe is
within
stand-off
space
12” pipe section
14-1/2”
(369 mm)
Stand-off
9-3/8”
(238 mm)
19-1/4”
(489 mm)
Fireplace
* 58” (1473 mm) with 12” vent pipe
* 47-1/2” (1207 mm)
36-1/2” (927 mm)
2-1/2”
(64 mm)
14-1/2”
(369 mm)
9-3/8”
(238 mm)
19-1/4”
(489 mm)
Fireplace
12” pipe section
*Notes—ALL venting considerations
Dimensions of venting are based on
using Dura-Vent elbows. Elbow curve
radius dimensions will vary when using
other brands and in general are slightly
bigger.
Minimum 12 inches vertical pipe section
required within vent system either right
off unit or downstream after horizontal
run. Refer to venting chart on page 29 for
allowable horizontal runs.
3 inches to combustibles required above
horizontal pipe. Slope pipe upwards 1/4
inch per foot. 1 inch clearance required
around sides and bottom of horizontal
pipe and around vertical pipe.
When calculating effective pipe lengths
subtract approximately 1-1/2 inch for
pipe joint - for example, a 12 inches pipe
section will add approximately 10-1/2
inches overall.
Venting Considerations—Vertical Takeoff
Venting Considerations—Horizontal Takeoff
Framing Requirements