Owner`s manual

29
2 4 6 8 10 12 14 16 18 20
VERTICAL RISE (ft)
HORIZONTAL RUN (ft)
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
4 x 90º ELBOWS MAXIMUM
(or equivalent)
Position #5
Example 1
NO INSTALLATION
Position #4
Position #3
Position #2
Position #1
Allowable Co-Axial Vent Con gurations
with restrictor positions
V2
V1
V3
H2
H1
Minimum 12”
pipe section
45° elbow take-off
supplied with unit
1” min.
all around
vertical pipe
3” min.
above top of
horizontal pipe
1” min. around
bottom & sides
of horizontal pipe
12” minimum
vert pipe rise
How to Read the Venting Chart
The chart below applies to co-axial roof or wall
termination.
1. Minimum 12 inch vertical pipe section required
within vent system either right off unit or down-
stream after horizontal run.
2. The total length of the vent pipe cannot exceed
40 feet.
3. The minimum vertical height with roof termination
is 6 feet.
4. Any combination of rise and run can be used as
long as they are within the allowable limits shown
on the chart below.
5. A maximum of 4 x 90 degrees elbows—or
equivalent (2 x 45 degrees = 90 degrees)—can
be used. Excludes the 45 degrees take-off elbow
shipped with the appliance.
6. Each 90 degrees elbow installed on the horizontal
plane is equivalent to a 3 feet horizontal pipe;
therefore, 3 feet must be subtracted from allowable
horizontal run. (45 degrees elbow is equivalent to
18 inches horizontal pipe.)
7. All horizontal pipe runs must be graded 1/4 inch per
foot upwards in the direction of the exhaust ow.
The nal pipe length, when terminating through the
wall may be graded downwards slightly to prevent
water migration.
8. A restrictor adjustment is required for most
installations having a vertical rise—see next
section.
Note: The restrictor is shipped installed at the
exhaust exit of the rebox.
Co-axial Venting
Venting Chart
Example 1
V Value = V1 (3’) + V2 (2’) + V3 (1’)= 6’
H Value = H1 (0’) + H2 (3’) = 3’
Restrictor position # 2 required
NO INSTALLATION
QUALIFIED
INSTALLER