Instruction Manual

REV 1 DIGITMR S2 USER’S MANUAL
30
3.4 General Procedures and Configuration
The main steps for timing a circuit breaker are listed in Figure 14 below.
Figure 14. DigiTMR S2 General Operating Procedures
NOTE
To reduce the possibility of damaging the DigiTMR S2 due to static discharge in high
voltage substations, it is recommended that one side of the breaker’s bushings be
grounded for the contact channels.
Get Test Results
View or print tabulated results
Print graphic results
Save timing shot
Time Breaker
Select DigiTMR S2 test
Operate Breaker
Connect the DigiTMR S2
Ground the DigiTMR (see note)
Connect the cables to the circuit breaker
Install the transducer and cable
Apply Power
Turn on the power for the DigiTMR S2. Once the
unit goes through its start-up cycle, the “Start-Up”
menu will be displayed.
Perform self test (hook-up test, cable test) if
necessary