After all of the contacts have been closed, the following screen will be displayed:
Fully close the breaker. When the breaker is at the close position (on latch), press the
[ENTER] key to find contact wipe.
e. The test results will be printed, and you will be returned to the “START-UP” menu. A
typical “Slow-Close” test results printout is shown in Figure 11.
NOTES
The “Slow-Close” test report can be saved in the DigiTMR’s EEPROM. Please see
section 3.8.1 for information on how to save test records.
You can calculate contact stroke by adding the contact touch and contact wipe
distances.
Figure 11. Typical "Slow-Close" Test Results Printout
LIFT BRKR TO CLS POS
THEN PRESS “ENTER”
TO FIND CONTACT WIPE
LIFT TO CLS BRKR NOW
CONTACT 1: CLOSED
CONTACT 2: CLOSED
CONTACT 3: OPEN
LIFT TO CLS BRKR NOW