3.10 Changing Setup Parameters
3.10.1. Setting Up Analysis Points
Analysis points are used to calculate the average contact velocity through the contact’s arc
zone. The analysis points are usually specified by the breaker’s manufacturer. The user can
enter the analysis points, and the DigiTMR will store the two setup points for calculating
velocity, one set each for the open and close operations.
NOTES
Average velocity through the arc zone is calculated by using the formula below:
V
ave
= Distance / Time
The breaker contact velocity is calculated based on data stored in the memory
after any analysis points were selected. The user does NOT need to operate the
breaker again to acquire new contact velocity data after changing the analysis
points because a new velocity is calculated from the travel data stored in
memory from the last operation.
The included VCBA PC software can be used for more complex velocity
calculations.
To set the OPEN analysis points:
a. Start from the “START-UP” menu:
Press the [3] key (SET-UP).
b. The following screen will be displayed:
Press the
[1] key (ANALYSIS POINTS).
1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
1. TIME BRKR 04/17/09
2. GET RSLT 10:49:23
3. SET-UP
4. DIAGNOSTICS