User guide

DIGITMR USER’S MANUAL REV 3
63
f. The following screen will be displayed:
Press the
[2] key (DIST FROM CLOSE).
NOTES
Option details
PERCENT OF STROKE
Percent of stroke is the distance based on the percentage of the total
breaker’s stroke distance. The distance is always measured from the
starting point at the fully closed position of the breaker contacts.
DIST FROM CLOSE
The distance from Close range is selectable from 00.0 inch to 99.99
inches or from 0.0 centimeter to 99.90 centimeters. The distance is
referenced from the contact’s closed position.
CONTACT +/-
For “CONTACT + TIME”, the user enters time in milliseconds after the
contact channel #1 made the transition from open-to-close or close-to-
open to define analysis point 2.
For “CONTACT – TIME”, the user enter the time in milliseconds before
the contact channel #1 makes the transition from open-to-close or
close-to-open to define analysis point 2.
g. The following screen will be displayed:
Press the [CLEAR] key and then press [2][0][0] to set the value at 2.00 in. Press the
[ENTER] key.
h. The OPEN analysis points will be set, and you will be returned to the “START-UP” menu.
OPEN ANALYSIS PT 2
DISTANCE FROM CLOSE
VALUE: 05.00 in
“ENTER” TO CONFIRM
OPEN ANALYSIS PT 2
1. PERCENT OF STROKE
2. DIST FROM CLOSE
3. CONTACT +/- TIME