User Manual
REV 1 TRM-203 AND TRM-403 USER’S MANUAL
53
1. YES
Press the [1] key (YES) if you wish to convert readings to standard temperature. The
following screen will be displayed:
Press the [1] key (COPPER, Tk=234.5) to select copper as the winding material.
Continue to step h.
Press the
[2] key (ALUMINUM, Tk=225) to select aluminum as the winding material.
Continue to step h.
Press the
[3] key (MANUALLY ENTER Tk) to manually enter the Tk value. The
following screen will be displayed:
You can increase the Tk value by 0.5°C increments by pressing the [∧] key.
You can decrease the Tk value by 0.5°C increments by pressing the
[∨] key.
Press the [ENTER] key to confirm the temperature setting. Continue to step h.
2. NO
Press the [2] key (NO) if you do NOT wish to convert readings to standard
temperature. Continue to step j.
TK:
230.0°C
↑↓ to adjust tk
"ENTER" to accept
WINDING MATERIAL:
1. COPPER, TK=234.5
2. ALUMINUM, TK=225.0
3. MANUALLY ENTER TK