User Manual

TRM-203 AND TRM-403 USER’S MANUAL REV 1
60
After the TRM has finished its internal calibration, the following screen will be displayed:
When the TRM has determined that the resistance reading is stable, the following
screen will be displayed:
Press the [ENTER] key or the LTC [RAISE] or [LOWER] key to continue.
h. The following screen will be displayed:
Press the
[1] key (LATCHED).
i. The TRM will start capturing data and the following screen will be displayed:
The second line on the screen will display the remaining time for the test. While the
TRM captures data, you can press the LTC
[RAISE] or [LOWER] button to cycle
through the LTC or Voltage Regulator’s taps. You can wait for the remainder of the test
time or you can press the [STOP] key at any time to end the test. If you have
RUNNING DYNAMIC
LTC TEST T=239
"STOP" TO END TEST
** XFMR ENERGIZED! **
TAP SWITCH OPERATION:
1. LATCHED
2. MOMENTARY
PRESS "ENTER" 00:01
OR LTC RAISE/LOWER
TO START TIMING...
I = 9.98 AMPS
*XFMR CHARGING*
please wait...
I = 1.90 AMPS
** XFMR ENERGIZED! **