Owners Manual

Preventive Maintenance and
Trouble Shooting Procedure
IT SERIES Industrial True Sine Wave Inverter Owners Manual
25
Problem:
Overload Indicator Light is ON when AC load is applied.
Check:
Verify AC load is within the inverter’s rated capacity. Remove excessive loads.
Problem:
DC fuse blows when connecting DC input cables.
Check:
Check for reverse polarity (Positive and negative DC cables reversed.)
Problem:
Excessive audible buzzing during inverter operation but inverter operates loads.
Check:
Check mounting bracket bolt tightness.
Problem:
AC loads do not seem to be fully energized when operating from inverter power.
Check:
Check AC output voltage at convenience receptacle. Check for overheated DC or AC wiring.
Verify AC load specifications are not exceeded.
Problem:
Unit does not operate and a “burnt wire” smell emits from inverter.
Check:
Disconnect AC loads and battery immediately. Unit may require service, contact Vanner
service department.