Brochure
Vanner Inc. 4282 Reynolds Dv., Hilliard, OH 43026
Tel: 1-800 AC Power Fax: +1 614 771 4904
e-mail: pwrsales@vanner.com web: www.vanner.com
© Copyright 2003 Vanner Inc.
• Inverter
The inverter consists of a
3200 watt sine wave inverter
which supplies power when
AC loads are applied. The
inverter develops up to 3200
watts of continuous power.
Using TruSine
®
technology, a
very high quality pure sine
wave is produced. Total
harmonic distortion (THD) is
less than 2.0 percent. The
inverter also has a 1 second
surge rating of 6400 Watts.
• Battery Charger with Automatic Power Management
A high efficiency 80 amp
multi-stage battery charger
allows fully automatic
charging of flooded and gel
lead acid battery banks.
The efficient 0.85PF,
compared to typical 0.59PF
on triac type chargers,
allows full charger output
from a 30 amp AC source.
The system’s Bulk -
Absorption - Float charge
cycle quickly charges and
maintains the charge on the battery bank. An Equalization charge cycle is provided
for flooded lead acid battery maintenance. Automatic Power Management (APM)
monitors the AC Input current and will reduce the battery charger output as needed
to keep the AC input current below the preset APM Limit.
• Gen Start/AutoThrottle
The Gen Start/AutoThrottle feature provides a start/stop signal to control a generator
used for recharging the batteries. The start/stop signal consists of a contact closure
to start the generator based on battery voltage and stop the generator based on
battery charging current.
• Low Battery Contact
This contact allows remote monitoring of the Inverter Battery status, closing a contact
when the battery voltage falls below 11 volts. This will allow the user to take
appropriate measures to avoid shutdown of the Inverter at 10.5VDC.
VOLTAGE
CURRENT
TIME
BULK
ABSORPTION
OPTIONAL
EQUALIZE
FLOAT
TRIGGER POINT