Owner`s manual

INCOR POR ATED
®
Installation
ITC-Series Inverter Page 18 10/07/05
AC Input & Output Wiring
The AC wiring compartment is located on the front right side of the unit. A removable access cover covers this
compartment. Two cable clamps are installed for the AC input and AC output wiring. The removable access
cover can be removed by simply removing the screws on the front panel of the unit (ONLY!). There is no need
to remove screws from the top or sides of the unit to gain access to the AC wiring compartment. Inside the
compartment is a terminal strip for making AC input and AC output connections (P14 and P15).
NOTE
The AC output voltage and the required AC input voltage of the ITC is 120 VAC, 60Hz.
DC (Battery) Wiring
A DC wiring compartment is located behind the wiring panel on the right side of the unit. The compartment
contains a removable access cover on the top of the inverter and two cable clamps for the battery positive and
battery negative cables. The inverter‟s battery cable terminal studs are 5/16-18 and can accommodate Cable
sizes up to 250 MCM.
Front Panel Control/Display Outlet
This is a RJ-11 (6-Wire) jack (P5) for communications with the Control/Display Unit. A secondary
GND
OPTIONS TERMINAL STRIP
P14
HOT NEU GND
AC INPUT
P15
HOT NEU GND
AC OUTPUT
P6
P5
REMOTE MASTER AND
SLAVE CONNECTORS
REMOTE
SWITCH
REMOTE LED
COM N/O N/O
LOW BATT/
FAN ON
COM
GENSTART
P3
BATTERY TEMP.
SENSOR
P7