VANNER Incorporated Owner’s Manual VLT Series 600 Watt True Sine Wave Inverter Pure Sine Wave Inverter ON INPUT LEVEL I 0 LOAD LEVEL OFF FAULT AC OUTPUT FREQ.
VANNER Incorporated Owner’s Manual TABLE OF CONTENTS 1 INTRODUCTION ................................................................................... 3 2 IMPORTANT SAFETY INSTRUCTIONS .............................................. 3 2.1.1 2.1.2 General Safety Precautions ........................................................................................................ 3 Precautions When Working With Batteries ...............................................................................
VANNER Incorporated Owner’s Manual 1 INTRODUCTION Thank you for purchasing a Vanner 600 Watt VLT SERIES Inverter. We are confident that you will be satisfied with the inverter’s performance and its many features. With proper installation and care, you can look forward to years of service from this high performance product. This document will describe the operation, technical specifications and installation procedures.
VANNER Incorporated Owner’s Manual 2.1.2 Precautions When Working With Batteries If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 20 minutes and get medical attention immediately. Never smoke or allow a spark or flame in vicinity of battery or Engine. Do not drop a metal tool onto the battery. The resulting spark or short-circuit on the battery or other electrical part may cause an explosion.
VANNER Incorporated Owner’s Manual 3 SPECIFICATIONS AND FEATURES 3.1.1 Specifications Model Number SPECIFICATIONS VLT12-600 VLT24-600 VLTE12-600 VLTE24-600 AC Power Output Rated Continuous Output 600 Watts Surge Rating (3S) A 6.67 3.
VANNER Incorporated Owner’s Manual 3.1.2 Front Panel Pure Sine Wave Inverter ON INPUT LEVEL I 0 LOAD LEVEL OFF FAULT AC OUTPUT FREQ. 50Hz 60Hz 3.1.2.1 ON / OFF Control Switch The ON/OFF Switch must be in the ON position when using Remote Control. 3.1.2.2 Input Level LED LED Display and Color 12Vdc 24Vdc Slow Red Blink 10.10 to 11.10 21.0 to 21.8 Red 11.10 to 11.60 21.8 to 22.6 Orange 11.60 to 13.20 22.6 to 24.0 Green 13.20 to 15.20 24.0 to 28.0 Orange Blink 15.20 to 16.00 28.
VANNER Incorporated Owner’s Manual 3.1.3 AC Output GFCI Duplex Receptacle The AC output neutral conductor is connected to AC ground and inverter chassis ground inside the inverter. This conforms to National Electrical Code requirements that separately derived AC sources (such as inverter and generators) have their neutral conductors tied to ground in the same way that the neutral conductor from the utility is tied to ground at the AC breaker panel.
VANNER Incorporated Owner’s Manual Remote Control via customer-supplied SPST switch: If it is desired to remotely control the inverter from a customer-supplied remote switch, remove the jumper connecting terminals Vout and Vin. Supply a 12v (24v signal on 24v units) continuous signal to terminal Vin to turn the inverter ON. The source of the 12v signal can be battery voltage for single-wire remote control or terminal Vout for two-wire-remote-control.
VANNER Incorporated Owner’s Manual 4 INSTALLATION Inverter Installation Considerations Mounting: Locate a flat secure, dry, horizontal or vertical surface large enough to mount the inverter. The location should be as close to the battery as practical, usually within six feet, but not in the same compartment and should provide adequate ventilation while the inverter is operating. The location must be clean, dry and free from road spray, dripping water or other moisture contamination.
VANNER Incorporated Owner’s Manual 4.1.1 DC Cable and Fuse Sizing Chart Model Number VLT12-600 VLT24-600 Distance from battery to inverter in feet (Total circuit length is 2 times the distance.) Wire Size 8 6 4 Fuse Rating 6.5 10.0 16.0 80 Amp 13.5 20 20 60 Amp Fuse Part Number 013910 013909 Fuse Holder Part Number 013780 DC Wiring Installation Procedure Verify the Power ON/OFF Switch is in the OFF position before connecting inverter to the battery.
VANNER Incorporated Owner’s Manual 5 TROUBLESHOOTING WARNING! Do not open or disassemble the Inverter. Attempting to service the unit yourself may result in a risk of electrical shock or fire, and will void warranty. Problems and Symptoms Possible Cause Solutions No AC output voltage accompanied by the following Power Status LED flash pattern. Blinking Red Fast. High DC input voltage. Blinking Red Slowly. Low DC input voltage.
VANNER Incorporated Owner’s Manual Vanner Incorporated 4282 Reynolds Drive Hilliard, Ohio 43026 Ph: 800-AC POWER Ph: 614-771-2718 Fax: 614-771-4904 www.vanner.