Operating instructions

26
380 – 480 VAC
Enclosure
IP 20 (IP 21*)/Chassis(Type 1) A2 A 3
IP 55 + IP 66 /Type 12 A4 + A5 A5
P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
Typical Shaft Output [kW] 1.1 1.5 2.2 3 4 5.5 7.5
Typical Shaft Output at 460 V [HP] 1.5 2.0 2.9 4.0 5.0 7.5 10
Output Current
(3 x 380 – 440 V)
Continuous [A] 3 4.1 5.6 7.2 10 13 16
Intermittent [A] 3.3 4.5 6.2 7.9 11 14.3 17.6
Output Current
(3 x 441 – 480 V)
Continuous [A] 2.7 3.4 4.8 6.3 8.2 11 14.5
Intermittent [A] 3.0 3.7 5.3 6.9 9.0 12.1 15.4
Output Power
(400 V AC)
Continuous [kVA] 2.1 2.8 3.9 5.0 6.9 9.0 11.0
Output Power
(460 V AC)
Continuous [kVA] 2.4 2.7 3.8 5.0 6.5 8.8 11.6
Max. cable size
(Mains, motor, brake)
[mm
2
]
([AWG])
4 (10)
Max. Input Current
(3 x 380 – 440 V)
Continuous [A] 2.7 3.7 5.0 6.5 9.0 11.7 14.4
Intermittent [A] 3.0 4.1 5.5 7.2 9.9 12.9 15.8
Max. Input Current
(3 x 441 – 480 V)
Continuous [A] 2.7 3.1 4.3 5.7 7.4 9.9 13.0
Intermittent [A] 3.0 3.4 4.7 6.3 8.1 10.9 14.3
Max. pre-fuses [A] 10 10 20 20 20 32 32
Environment
Estimated power loss at rated max. load [W] 58 62 88 116 124 187 255
Weight
IP 20 [kg] 4.8 4.9 4.9 4.9 4.9 6.6 6.6
IP 55, IP 66 [kg] 13.5 13.5 13.5 13.5 13.5 14.2 14.2
Effi ciency 0.96 0.97 0.97 0.97 0.97 0.97 0.97
* (A2, A3, B3, B4, C3 and C4 may be converted to IP21 using a conversion kit. Please contact Danfoss.
(Please see also items Mechanical mounting in Operating Instructions and IP 21/ Type 1 Enclosure kit in the Design Guide.))
1) With brake and load sharing 95 (4/0)
Enclosure
IP 20 (IP 21*)/Chassis(Type 1) B3 B 4 C3 C4
IP 21/Type 1, IP 55 + IP 66/Type 12 B1 B2 C1 C2
P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 11 15 18.5 22 30 37 45 55 75 90
Typical Shaft Output at 460 V [HP] 15 20 25 30 40 50 60 75 100 125
Output Current
(3 x 380 – 439 V)
Continuous [A] 24 32 37.5 44 61 73 90 106 147 177
Intermittent
[A] 26.4 35.2 41.3 48.4 67.1 80.3 99 117 162 195
Output Current
(3 x 440 – 480 V)
Continuous [A] 21 27 34 40 52 65 80 105 130 160
Intermittent
[A] 23.1 29.7 37.4 44 61.6 71.5 88 116 143 176
Output Power
(400 V AC)
Continuous [kVA] 16.6 22.2 26 30.5 42.3 50.6 62.4 73.4 102 123
Output Power
(460 V AC)
Continuous [kVA] 16.7 21.5 27.1 31.9 41.4 51.8 63.7 83.7 104 128
Max. cable size
Mains, motor, brake
[mm
2
]
([AWG])
10 (7) 35 (2)
50 (1/0)
(B4 = 35 (2))
95 (4/0)
120 (250
MCM)
1)
Max. cable size mains
With mains disconnect switch included
[mm
2
]
([AWG])
16 (6) 35 (2) 70 (3/0)
185
(kcmil
350)
Max. Input Current
(3 x 380 – 439 V)
Continuous
[A]
22 29 34 40 55 66 82 96 133 161
Intermittent
24.2 31.9 37.4 44 60.5 72.6 90.2 106 146 177
Max. Input Current
(3 x 440 – 480 V)
Continuous
[A]
19 25 31 36 47 59 73 95 118 145
Intermittent
20.9 27.5 34.1 39.6 51.7 64.9 80.3 105 130 160
Max. pre-fuses [A] 6363636380100125160250250
Environment
Estimated power loss at rated max. load [W] 278 392 465 525 698 739 843 1083 1384 1474
Weight
IP 20 [kg] 12 12 12 23.5 23.5 23.5 35 35 50 50
IP 21, IP 55, IP 66 [kg] 23 23 23 27 27 45 45 45 65 65
Effi ciency 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.99