The C-Box typically uses RX, TX and GND for RS-232 communications. RTS and CTS are also implemented for hardware that
requires them.
The default protocol for RS-232 communication is:
Signal Format: Conforms to RS-232 C standard
Baud: 19200
Parity: none
Total Bits: 8
Stop Bits: 1
Flow Control: None
D. NOTE
The C-Box provides +24VDC at 100mA and +12VDC at 250mA. These voltages are available for external hardware such as motion
detectors, light sensors, etc.
C-Box low-voltage circuits are classified as Class 2 circuits (USA). As Class 2 circuits, they comply with the requirements of NFPA 70, National
Electrical Code (NEC). When installing and wiring to these C-Boxes, follow all applicable national and/or local wiring regulations. External
connections to any low-voltage C-Box terminal must be from a Listed Class 2 Source.
5. PLUG C-BOX INTO AC RECEPTACLE
After carefully checking all low-voltage wiring, (if any), proceed to plug the C-Box into a grounded AC
receptacle using the supplied power cord. Although not suggested, if additional length is required, a
longer cord may be used as long as it contains a ground conductor.
6. SETUP SOFTWARE
A. LCD Control & Menu Structure
Overview:
The front panel of the C-Box has five buttons that allow control of, or status of the following elements:
1. Set Load Levels By:
a. Master
b. Module
c. Load
d. Level, Toggle or Increment (10%)
2. Set Station Switch Status (not implemented)
3. Set Master Time
a. Time
i. Month/Date/Year/Hour/Minute/Second
b. Calibrate Time Clock
i. '+' or '
-
' number of seconds per day
4. Diagnostics of:
a. Master
i. Version
ii. Network Communications
iii. TeleAccess Installed Status: Yes/No
iv. Generate - Displays Master Address
b. Station (not implemented)
c. RS232
i. Displays Current RS 232 Settings Only, i.e. 19200, N, 8, 1
d. Gen (Generate)
i. Load Backup Flash (reprogram C-Box from Flash Memory)
FRONT VIEW OF PORT-C
& DIAGNOSTIC PORT
C-BOX RS-232 CONNECTIONS
Signal
Name
RX Data In
TX Data Out
GND
CTS
RTS
Vantage
DB9 Pin
2
3
5
7
8
Screw
Terminals
3
2
1
4
5
External Devices
Data out (TX)
Data In (RX)
Ground (GND)
Handshake Out (RTS)
Handshake In (CTS)
100-250V AC
50/60Hz