8310 TGI Hardware
Varec, Inc. 7
2.2.1 Power Supply
Unit AC Power terminal block (J2)
Surge Protection terminal block (J4)
Field Power terminal block (J3)
Auxiliary DC Power Output terminal block (J8)
AC Power fuses (500 mA - 250V 5x20 mm) (F1, F2)
Field Voltage Selection Jumper (W3)
2.2.1.1 Unit AC Input Power terminal block (J2)
The Unit AC power terminal block is used to provide AC power to the Tank Gate Interface. The
power requirements for the Tank Gate Interface are 100-240 VAC, 50/60 Hz. The AC Input
Power terminal block is shown in the figure below.
Figure 2-4: AC Input Terminal Block
2.2.1.2 Surge Protection (Surge Gnd) terminal block (J4)
The Surge Gnd terminal block is used to connect the surge protection components (gas tubes,
MOVs) to earth ground. Ensure there is a low impedance path (< 1ohm) to earth ground (a
ground rod or grounding system).
EARTH
NEUTRAL
LINE
SURGE GND
+
-
VFIELD
J2
J4
EARTH
EARTH
NEUTRAL
NEUTRAL
LINE
LINE
SURGE GND
SURGE GND