Instruction manual

8310 TGI Hardware
Varec, Inc. 9
2.2.1.5 AC Power Fuses (F1,F2)
The AC Power Fuses provide protection for the AC input power. The two fuses, F1 and F2, are
rated at 500 mA, 250 V.
Figure 2-7: AC Power Fuse
2.2.1.6 Field Voltage Selection Jumper (W3)
The Field Voltage Selection Jumper W3 determines the voltage available at the VFIELD terminals
(J3). The Field Voltage can be configured for +24 VDC or +48VDC. At +24VDC, there is 230 mA
of field power available. At +48VDC, there is 230 mA of field power available.
Figure 2-8: Selection Jumper W3
2.2.2 Switches and Indicators
2.2.2.1 Reset push-button (SW3)
The RESET Switch is used to re-initialize the system hardware by causing it to go to a known
starting state. This switch may be pressed at any time; however, it will do the following: