The number of gauges scanned during a Fast Scan Cycle is determined by the FastScanMax. If
the value is 0, then all MSTX, MSSTG and GS2000 points with the FastScanMode set to Enable
will be scanned. If the value is 1, then only a single gauge from the Fast Scan List will be read
each time a Fast Scan Cycle is executed.
The Interleave parameter controls the number of gauges read during each Normal Scan Cycle.
Example – Default method, with 1 tank in the Fast Scan List
Interleave = 1, FastScanMax=0, FastScanTime=00:00:00, MSTX.00.FastScanMode = Enable (ID
= 1).
Example – One tank in the Fast Scan List
Interleave = 3, FastScanMax=0, FastScanTime=00:00:00, MSTX.00.FastScanMode = Enable (ID
= 1).
Setting the Interleave to 3 results in 3 tanks being read each time a Normal Scan is performed.
Example – Six tanks in the Fast Scan List
Interleave = 3, FastScanMax=2, FastScanTime=00:00:00, MSTX.00.FastScanMode
MSTX.05.FastScanMode = Enable (Ids 1-6)
Setting the Interleave to 3 results in 3 tanks being read each time a Normal Scan is performed.
Setting the FastScanMax to a 2 results in 2 tanks being read each time a Fast Scan is performed.
NumFastScan Number of points in the Fast Scan List
(Fast Scan shown in shaded cells)
1
12131415161718…
(ID = 1).
123
145617891 101112…
(Ids 1-6)
123
1 24563 47895 6…
Parameter Description