Instruction manual

Configuration Tank Gauge Transmitter
16 Installation and Operations Manual
3.4.2 Summary Menu
Summary Menu Description
Level Current level.
Temperature Current temperature
RTD Resistance RTD resistance measured
Cfg Error Type Configuration error type detected.
Power Log Number of times unit has gone through a power down cycle
since it was last configured. Going into Alter Mode and using
'Exit and Save' resets this value to 0.
Bad CPU Board Stat
3
Bad CPU Board Stat3True if the RAM, ROM, or EEPROM are bad.
Bad RAM Stat
3
True if RAM status is bad.
Bad EProm Stat
3
True if EProm status is bad.
Bad EEProm Stat
3
True if EEProm status is bad.
Bad EECksum Stat
3
True if EEProm checksum does not match the data stored in it.
Bad Comm Board
3
True if communication board failed loopback test
Bad Level Stat
3
True if level is bad.
Bad Temp Stat
3
True if temperature input is out of range.
Low Battery Stat
3
True if battery voltage is low or no battery is connected.
Crit Hi Level Stat
3
True if the level is above the critical high level setpoint
Adv Hi Level Stat
3
True if the level is above the advisory high level setpoint
Adv Lo Level Stat
3
True if the level is below the advisory low level setpoint
Crit Lo Level Stat
3
True if the level is below the critical low level setpoint
Crit Hi Temp Stat
3
True if the temperature is above the critical high temperature
setpoint
Adv Hi Temp Stat
3
True if the temperature is above the advisory high temperature
setpoint
Adv Lo Temp Stat
3
True if the temperature is below the advisory low temperature
setpoint
Crit Lo Temp Stat
3
True if the temperature is below the critical low temperature
setpoint