In the tank database of the 2410 Tank hub, the 2240S temperature transmitter and the 2230
display are grouped into an Auxiliary Tank Device (ATD). The ATD Modbus address has to be
stored in the Temperature Device address field in the tank database of the 2460 System Hub as
illustrated in Figure 4-5 on page 60. The Modbus addresses of the level devices must also be
stored in both the 2410 and the 2460 tank databases.
Figure 4-5. The Tank Database of the 2460 System Hub must match the Tank Databases of connected 2410
Tank Hubs
Note that in this example a single 2410 Tank Hub serves three tanks. The tanks are mapped to
tank position 1, 2, and 3 in the Tank Database of the 2410 Tank Hub.
In the Tank Database of the 2460 System Hub, you will have to configure 2410 Tank Position in
order to be able to configure the correct Temperature Device Addresses for the three tanks.
2460 System Hub
Tank Database for a 2410 Tank Hub that serves three tanks
Level device address
Auxiliary Tank Device (ATD)
address