Technical Information Tank Side Monitor NRF590 Inventory Control Field device for tank sensor operation and monitoring and for integration into inventory control systems Software Version 02.03. Application The Tank Side Monitor NRF590 is a sensor integration and monitoring unit for bulk storage tank gauging applications. It can be used with Micropilot level radars and combined with other HART compatible devices. The Tank Side Monitor offers the following functions: • intrinsically safe (i.s.
Table of Contents Function and system design. . . . . . . . . . . . . . . . . . . . . 3 Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 System Integration (typical example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 HART interface . . . . . . . . . . . . . .
Function and system design Application The Tank Side Monitor NRF590 is a field device for the integration of tank sensors into tank inventory systems. It is used in tank farms, terminals and refineries. Especially, it can be used in connection with Micropilot M level radars (for inventory control) and Micropilot S high accuracy level radars (for custody transfer applications).
HART interface IS (intrinsically safe) HART Master for measuring device connection Non-IS (if selected by order code) user settable: • HART Master • HART Slave (active 4-20 mA when address is "0") Power supply for HART instruments The Tank Side Monitor provides intrinsically safe power for 2-wire tank sensors. It also can provide intrinsically safe power for the 4-wire instrument Micropilot S.
Typical Tank calculations Setup preset Installation example Sensors measured/ calculated values required parameters • Level sensor • level • Tank Ref Height Direct level measurement Level only Micropilot Tank Ref Height Tank Side Monitor L00-NRF590-14-00-08-yy-002 Level + Temperature Micropilot Prothermo Tank Side Monitor • level • Level sensor • Temperature sensor • temperature (RTD or HART device; optionally with bottm water probe) L00-NRF590-14-00-08-yy-003 Hybrid Tank Measuring System
Setup preset Installation example Sensors measured/ calculated values required parameters • Pressure sensor (P1, bottom) • level (calculated) • • • • • level (calculated) • density of the measured medium (calculated) • Tank Ref Height • local gravity • Min HTG Level (minimum level at which HTG measurement is possible; should be slightly above the position of the P2 sensor) • P1 Position • P1-P2-Distance • P3 Position (only for the "HTG P1,2,3" mode) Hydrostatic Tank Gauging (HTG) HTG P1 Tank Side
Corrections The Tank Side Monitor can automatically calculate the following corrections: • Correction for the Hydrostatic Tank Deformation (HyTD) • Temperature Correction for Thermal Expansion of the Tank Shell (CTSh) Flow calculation (in preparation) The Tank Side Monitor can calculate the approximate flow based on the rate of level change and a linear conversion, to volumetric flow.
Inputs and outputs V1 Modbus WM550 Enraf BPM Mark/Space L&J GPE Non-i.s. terminals Ex d Power AC/DC Fieldbus 4...20 mA Analogue In (option) 4...20 mA 4...20 mA Analogue Out 1 Analogue Out 2 with HART (option) (option) Discrete In/Out A Discrete In/Out B Discrete Out C (option) (option) (option) HART (up to 24 mA) FMR Spot RTD (option) Pressure transmitter NMT i.s. terminals Ex ia Analogue In Discrete In 1 Discrete In 2 4...
Fieldbus Protocols The Tank Side Monitor NRF590 supports all of the following industry standard communication protocols allowing it to be integrated with existing instrumentation and connect to host computer systems without the need for additional hardware. These protocols allow for piece-by-piece replacement and upgrading of older technologies to modern radar solutions. Sakura V1 V1 protocol provides a standard form of digital communication via a two-wire system.
Values transmitted by the Field Protocols The following values can be transmitted by the communication protocols: Symbol V1 - old V1 - new Modbus WM550 BPM Mark/ Space L&J Tankway Basic L&J Tankway Servo GPE Level L yes yes yes yes yes yes yes yes yes Temperature (Product) TP yes yes yes yes yes yes yes yes yes Observed Density Dobs - yes yes yes yes - - yes - Water Level LW - yes yes yes yes - - yes - yes yes1 yes - - - - 1) - - - - - Tan
Technical data of the non-IS inputs and outputs Analogue 4...20 mA input (option, s. pos. 20 of the product structure) Internal load (to ground) 110 Ω Measuring range 0 ... 26 mA Accuracy ±15 µA (after linearisation and calibration) Analogue 4...20 mA outputs Output current 3 ... 24 mA Output voltage U = 24 V - ILOAD 400 Ω Output load max. 500 Ω Accuracy ±15 µA (after linearisation and calibration) HART options1) • Slave, address # 0: 4 ...
Technical Data of the IS inputs and outputs HART input loop Source voltage U = 25 V - ILoad x 333 Ω (typically) total Imax Start-up currents of all connected HART devices may not exceed a total of 27 mA connectable sensors depending on current consumption (including start-up current) Spot RTD input (option, s. pos. 40 of the product structure) Measuring range 10 ... 600 Ω Excitation current typ. 400 µA, max.
Auxiliary energy AC supply 55 ... 264 VAC; insensitive to polarity / CSA approved: 55 ... 250 VAC DC supply 18 ... 55 VAC/DC Power consumption • • • • Fuse Internal (on primary power) Grounding The NRF590 must be grounded to the tank potential before communication and power connections are made. The connections (A ≥ 4mm2) from each outer ground plug of the NRF590 to the tank ground must be made before any other wiring connections are made.
Electrical connection - non-i.s.
Terminal 01 L/+ 02 N/Power supply 04 A1/+ 05 A2/- 06 B1/+ 07 B2/- 00 S Discrete I/O A + Discrete I/O A - Discrete I/O B + Discrete I/O B - Cable screen 08 C1 09 C2 10 C3 11 C4 12 C5 13 C6 14 C7 15 C8 V1 4 ... 20 mA output1) #2 V1A V1B 0 V1 0V 4 ... 20 mA output #1 + HART discrete output 1C discrete output 2C EIA-485 Modbus not used2) 485-B 485-A 0V 0 V1 4 ... 20 mA output3) +HART 4 ... 20 mA input3 +24 V1 Whessoe WM550 4 ...
Connection of the field protocols Sakura V1 The V1 protocol provides 2 wire communication allowing up to 10 devices to operate on a loop. V1 connects to terminals 9-10. Max. distance: 6000 m EIA-485 Modbus The NRF590 protocol uses a shielded 3-wire EIA-485 hardware interface to communicate with the modbus master. EIA-485 is a high speed, differential communications network that allows up to 32 devices to operate on one network.
Connection of the auxiliary energy The Tank Side Monitor can be AC or DC supplied, depending on the installed power supply board. The AC supply needs to be connected to the terminals marked L/+ (Line) and N/- (Neutral), corresponding with the phase/line and neutral wire. DC supply can be connected to the same terminals, for which it is necessary to connect the positive (+) to the terminal marked (L/+), and the negative to the terminal marked (N/-). Connection of the non-i.s. 4 ...
Electrical connection - i.s. terminals Terminal assignment NRF590 - i.s. terminal board RTD mA 24V Internally HART interconnected sensor as one HART fieldbus loop For Micropilot S-series only! L00-NRF590-04-00-08-en-018 18 Terminal Designation Meaning 16 D+ + RTD drive1) 17 S+ + RTD sense1 18 S- - RTD sense1,2) 19 D- - RTD drive1,2 20 OPT1 Discrete Input 1 21 OPT2 Analog Input 1 (4 ... 20 mA) 22 OPT3 Discrete Input 2 23 OPT4 Option +24 V 24 H+ +HART comm.
Connection of HART instruments Tank sensors The Tank Side Monitor can interface to a maximum of 6 i.s. HART sensors. All HART sensors are connected to one HART multi-drop communication loop. In order to keep wiring simple, 3 interconnected terminal pairs are available. The terminal pairs are marked respectively H+ and H-. Power supply for Micropilot S For supplying extra i.s. power to the FMR S-series radar, additional power terminals are available, marked as P+ and P-.
Performance characteristics Accuracy HART sensors Accuracy of all data from connected HART sensors depends on the type and installation of instruments. The use of the digital HART protocol prevents accuracy data degradation, as would be the case with analogue (4...20 mA) sensors. Spot RTD input, analogue inputs, analogue outputs see above, "Technical data of the IS inputs and outputs Resolution Resolution of all measured data depends on sensor and communication settings.
Installation conditions Ø 8.6 (M8) 3.94" (100 mm) Wall mounting 3.94" (100 mm) L00-NRF590-17-00-06-xx-001 Mounting on vertical rail 3.5" (90 mm) maximum Rail mounting kit (Order No.
Mounting on horizontal rail Rail mounting kit (Order No.: 52013134) Ø3.
Ambient conditions Ambient temperature -40 °C ... +60 °C (-40 °F ... +140 °F ) Storage temperature -55 °C ... 85 °C (-67 °F...185 °F) Ingress protection IP65, Nema 4X Electromagnetic compatibility (EMC) • Interference emission to EN 61326, Equipment class A • Interference immunity to EN 61326 Use shielded signal lines for installation.
Mechanical construction Design, dimensions L00-NRF590-06-00-06-yy-001 Construction The NRF590 housing has three separate compartments, one containing all electronics and two for electrical connections. The enclosure is die-cast aluminum with an polyester coating and IP65 (NEMA 4) rating. The upper terminal compartment and electronics compartment are designated for non-i.s. connections and electronics and are rated EEx d.The lower terminal compartment is designated for i.s.
Human interface Display and operating elements Liquid crystal display (LCD) Four lines with 20 characters each. Display contrast adjustable through key combination. The backlight of the display is activated during operation for user defined time (30 sec ... continuous backlight).
Format of decimal numbers The number of decimal places displayed can be selected from three resolution presets (high, normal, low) VAlue resolution preset low normal high mm xxxxx xxxxx xxxxx.x cm xxxx.x xxxx.x xxxx.x m xx.xxx xx.xxx xx.xxxx in xxxx.x xxxx.x xxxx.xx ft xxx.xxx xxx.xxx xxx.xxxx ft-in-8 xx’xx"x/8 xx’xx"x/8 xx’xx"x/8 ft-in-16 xx‘xx"xx/16 xx‘xx"xx/16 xx‘xx"xx/16 16ths xxxxx xxxxx xxxxx.x °C xxx xxx.x xxx.xx °F xxx xxx.x xxx.
Operating concept The Tank Side Monitor is operated via a four-layer menu. The structure of the menu accounts for typical measuring tasks as well as for the individual instrument configuration and installation. In particular, the menu contains dynamic function groups which are only indicated if the respective option is installed or the respective instrument is connected. This structure ensures clarity and simple operation without restricting the scope of functionality.
Certificates and Approvals CE mark The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark.
External standards and guidelines EN 60529 Protection class of housing (IP-code) EN 61010 Safety regulations for electrical devices for measurement, control, regulation and laboratory use. EN 61326 Emissions (equipment class B), compatibility (appendix A - industrial use) API MPMS Ch. 3.1A Standard Practice for Manual Gauging of Petroleum and Petroleum Products in Stationary Tanks. API MPMS Ch. 3.
Ordering information Product structure Ordering structure Tank Side Monitor NRF590 10 Certificates A 6 U S K Y 20 For non-hazardous areas ATEX II 2 (1) EEx d (ia) IIC T4 CSA XP Cl. I, Div 1, Gr. A-D FM XP Cl. I, Div 1, Gr.
80 Glands/Entries - non IS F B C D E H K L G Y 90 2 x G 1/2" gland (in preparation) 2 x Ex d M20x1.5 entries 2 x Ex d G 1/2" entries 2 x Ex d 1/2" NPT entries 2 x Ex d 3/4" NPT entries 3 x Ex d M20x1.5 entries 3 x Ex d G 1/2" entries 3 x Ex d 1/2" NPT entries 3 x Ex d 3/4" NPT entries (in preparation) Special version, to be specified Gland/Entry - IS compartment 2 3 4 5 9 100 M25x1.5 glands, 13...
Accessories Discrete I/O modules Standard mechanical diagram for all I/O modules 1.70 (43.1) 1.00 (25.4) 1.00 (25.4) .25 (6.35) 5 4 3+ 2 1 .30 (7.6) .200 (5.1) .700 (17.8) 1.100 (27.9) 1.30 (43.1) 1.70 (43.1) BOTTOM VI EW .040 (1.0) DIA. (5 PLACES) .100 (2.5) .40 (10.
Output modules AC voltage DC voltage + 1 1 VAC VAC/DC - Zero Voltage Circuit 2 + 2 Amplifier 3 Logic 3 Logic 4 4 NRF590 order code1) module A NRF590 ****J****** NRF590 ****G****** NRF590 ****H****** NRF590 ****K****** NRF590 order code1 module B NRF590 *****J***** NRF590 *****G***** NRF590 *****H***** NRF590 *****K***** Order Code2) Colour of housing Load voltage 52012959 52012960 52012961 52012962 black black red red 24 ... 140 V AC 24 ... 250 V AC 3 ... 60 V DC 4 .
Input modules AC voltage DC voltage + 1 1 VAC/DC VDC – 2 Logic 2 + Logic 3 3 Out Ground 4 Out - Schmitt Trigger 4 Ground 5 5 NRF590 order code1) module A NRF590 ****B****** NRF590 ****D****** NRF590 ****C****** NRF590 ****E****** NRF590 order code1 module B NRF590 *****B***** NRF590 *****D***** NRF590 *****C***** NRF590 *****E***** Order code2) Colour of housing Input voltage 52012955 52012956 yellow yellow 3) 52012957 52012958 white white 3 ... 32 V DC 35 ...
Relay output module 1 VAC /VDC 2 +VCC 3 AMP INPUT GROUND NRF590 order code1) module A NRF590 - ****R****** NRF590 order code1 module B NRF590 - *****R***** Order code2) 52026945 Colour of housing red Load voltage 0 ... 100 VDC / 0 ... 120 VAC Load current 0 ... 500 mA3) Max. contact resistance Max. turn on/off time4) 4 5 250 mΩ 1 ms Min.
Rail mounting kit For rail mounting the Tank Side Monitor to vertical or horizontal pipe.
Supplementary Documentation Special Documentation SD 001V Special Documentation - Radar Tank Gauging Technical Information TI 006G Technical Information Fuels Manager TI 007G Technical Information RTU 8130 TI 042N Technical Information Prothermo NMT 539 TI 216P Technical Information Cerabar S PMC 731 / PMP 731 TI 217P Technical Information Cerabar S PMC 631 / PMP 635 TI 344F Technical Information Micropilot S FMR 530/531/532/533 TI 345F Technical Information Micropilot M FMR 230/231/240/244/245 Operatin
International Head Quarter Endress+Hauser GmbH+Co. KG Instruments International Colmarer Str. 6 79576 Weil am Rhein Deutschland Tel. +49 76 21 9 75 02 Fax +49 76 21 9 75 34 5 www.endress.com info@ii.endress.com TI402F/00/en/07.06 FM+SGML 6.