Specifications

LA Series Linear Servo Amplifier Technical Reference Manual
13
8 LA-525 Jumper Settings
JP1 JP2
A B C D E F G H A B C D E F
JP3
Figure 3. Jumper Locations
JP1
Overcurrent Trip Level
Trip Current JP1-A JP1-B
4.0 Amps Open Open
6.0 Amps In Open
8.0 Amps Open In
10.0 Amps In In
Overcurrent Trip Time
Trip Time JP1-C JP1-D
1.25 Sec Open Open
2.50 Sec In Open
5.00 Sec Open In
10.0 Sec In In
Absolute Overcurrent Trip Level
Trip Current JP1-E JP1-F
15.0 Amps Open Open
20.0 Amps In Open
25.0 Amps Open In
30.0 Amps In In
JP1-G, Not Used. See Note 3
Motor Reverse Selection (Hall Mode)
Mode JP1-H
JP2
Sine/Hall Mode Selection*
Mode JP2-A
Sine Mode Open
Hall Mode In
*See Note 3
Input Filter Setting
Filter JP2-B JP2-C
500 Hz Open Open
800 Hz In Open
15,000 Hz Open In
32,000 Hz In In
Transconductance Ratio Setting
Ratio JP2-D JP2-E
1.0 Open Open
1.5 In Open
2.0 Open In
2.5 In In
Input DAC Selection
DAC Input JP2-F
Differential (Bipolar) Open
Single Ended (Unipolar) In
Normal Open
JP3
Reverse In
Current Loop Bandwidth Setting
Bandwidth JP3-A JP3-B
Contact Open Open
Factory In Open
For Open In
Settings In In
Note1: Jumper settings are only updated following a reset or POR of the drive.
Note2: If no jumpers are installed on JP1, JP2 and JP3, the parameters will be set via software.
Note 3: If using jumpers in Sine Mode with minimum settings (no jumpers), install a jumper on JP1-G to
force the drive to use the jumper settings. This prevents the drive from using software settings as
described in Note 2.
A B
See factory supplied configuration sheet
for “as delivered” amplifier values.