Installation guide
DEC 7000 AXP System and VAX 7000 System 1-3
The values in Table 1-1 apply to the system cabinet only. The values are
configuration dependent. Additional options will increase electrical re-
quirements so that an additional power regulator may be needed.
Table 1-1 Electrical Characteristics
Table 1-2 Environmental Characteristics
Electrical Specification
3-phase AC input
voltage
202 V RMS
120/208 V RMS
380–415 V RMS
Nominal frequency
50–60 Hz
AC current, nominal,
(per phase)
24 A (202 V)
24 A (120/208 V)
12.8 A (380–415 V)
Maximum current
(per phase)
30 A (202 V)
30 A (120/208 V)
16 A (380–415 V)
AC power consumption
(maximum)
5.2 KVA
5.2 KW
Environmental Operating Storage
Heat dissipation
17,700 Btu/hr (max) –
Temperature
1
15°–28° C (59°–82° F) -40°–66° C (-40°–151° F)
Relative humidity
1
20–80% 10–95%
Altitude
0–2.4 km (0–8000 ft) 0–9.1 km (0–30,000 ft)
1
Recommended operating temperature is 18°–24° C (65°–75° F) and 40–60% relative hu-
midity.