2.3.2 Power Surge Protection
Use the surge suppressor to protect your equipment and secure your data from power surges.
To connect the Cablefeed Shield to the Surge Suppressor Ground Lug
1. Remove the suppressor unit cover.
2. Thread the Ethernet cable through the right side opening to the suppressor.
3. Measure five (5) inches from the end of the cable that you threaded through the right side opening.
4. Lightly score the cable at the five inch mark.
5. Carefully slice the edge of the insulation.
Note: Do NOT cut the metal shield that surrounds the wires.
6. Slowly snip or slice the insulation down to the five (5) inch scoring.
7. Remove the insulation from the cable.
8. Gently twist the metal shield to form metal ground strip.
9. Make a straight-through cable with the wires.
Remember: be careful not to damage the metal ground strip.
10. Undo the grounding bolt on the right side of the suppressor.
11. Wrap the grounding strip onto the grounding bolt.
12. Screw the grounding bolt back into the side of the suppressor.
13. Thread the cable that connects to the Power over Ethernet through the left opening on the suppressor.
14. Strip the wires and make it a straight-through cable.
15. Connect the cables to their perspective ports.
16. Replace the cover of the suppressor.
17. Finish connecting the network. See “2.3.3 Grounding the Base Station”
Figure 2-10 Assembled Surge Suppressor