Specifications
Section 1
General Information
Appendix A-3MN722
Table A-2 Power Output Parameter Block Values Level 1 Continued
Level 1 Blocks - Continued
Block Title Parameter P# Adjustable Range Factory User
Setting
INPUT OPERATING MODE 1401 1− KEYPAD
2− STANDARD RUN
3− 15SPD
4− 3SPD ANA 2WIRE
5− 3SPD ANA 3WIRE
6− SERIAL
7− BIPOLAR
8− PROCESS MODE
9− EPOT −2WIRE
10− EPOT −3WIRE
KEYPAD
COMMAND SELECT 1402 0− POTENTIOMETER
1− +/-10 VOLTS
2− +/-5 VOLTS
3− 4 To 20 mA
4− 10V W/TORQ FF
5− EXB PULSE FOL
6− 5VOLT EXB
7− 10 VOLT EXB
8− 4-20mA EXB
9− 3-15 PSI EXB
10− TACHOMETER EXB
11− SERIAL
12− NONE
+/-10
VOLTS
ANA CMD INVERSE 1403 0−OFF, 1− ON OFF
ANA CMD OFFSET 1404 -20.0 TO +20.0%
(where ±0.5V=±20%)
0.0 %
ANA 2 DEADBAND 1405 0-10.00 V 0.00 V
ANA 1 CUR LIMIT 1406 0−OFF, 1− ON OFF
OUTPUT OPTO OUTPUT #1 1501 0− READY
1− ZERO SPEED
2− AT SPEED
3
−
OVERLOAD
READY
OPTO OUTPUT #2 1502
3
−
OVERLOAD
4− KEYPAD CONTROL
5− AT SET SPEED
6− FAULT
7− FOLLOWING ERR
8− MOTR DIRECTION
ZERO
SPEED
OPTO OUTPUT #3 1503
8
−
MOTR DIRECTION
9− DRIVE ON
10− CMD DIRECTION
11− AT POSITION
12 OVER TEMP WARN
AT SPEED
OPTO OUTPUT #4 1504
12− OVER TEMP WARN
13− PROCESS ERROR
14− DRIVE RUN
15− SERIAL
FAULT
ZERO SPD SET PT 1505 1-MAX Speed 200 RPM
AT SPEED BAND 1506 1-1000 RPM 100 RPM
SET SPEED 1507 0-MAX Speed Rated Motor
Speed
Status on/off
System in operation
Drive not operable