Program Mode Continued
Initialize New Firmware
After new firmware is installed, the control must be initialized to the new firmware version
and memory locations. Use the following procedure to Initialize the firmware.
Action
Description Display Comments
Apply Power Keypad Display shows this
opening message.
Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation.
Display mode. Stop LED on.
Press PROG key Enter program mode.
Press or key
Scroll to Level 2 Blocks.
Press ENTER key Select Level 2 Blocks.
Press or key
Scroll to the Miscellaneous block.
Press ENTER key Select Miscellaneous block.
Press key
Scroll to Factory Settings
parameter.
Press ENTER key Access Factory Settings
parameter.
represents blinking cursor.
Press key
Scroll to YES, to choose original
factory settings.
Press ENTER key Restores factory settings. “Loading Presets” is first message
“Operation Done” is next
“No” is displayed last.
Press key
Scroll to menu exit.
Press ENTER key Return to display mode. Display mode. Stop LED on.
Press DISP key several
times
Scroll to diagnostic information
screen.
If you wish to verify the software
version, enter diagnostic info.
Press ENTER key Access diagnostic information. Displays commanded speed,
direction of rotation, Local/
Remote and motor speed.
Press DISP key Display mode showing software
version and revision installed in
the control.
Verify new firmware version.
Press DISP key Displays exit choice. Press ENTER to exit diagnostic
information.