Operating instructions

Vector Control Chassis Type Frequency Converter Parameterizing steps
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 9-39
P068 = ?
Input unit line voltage in V
AC units: r.m.s. alternating voltage
DC units: DC link voltage
P060 = 5
Select "Drive setting" menu
P071 = ?
Output filter
0 = without output filter
1 = with sinusoidal output filter
2 = with dv/dt output filter
P095 = ?
Enter type of motor
10: Induct. IEC (international standard)
11: Induct. NEMA (US standard)
12: Sync. motor, separately excited (special applications)
13: Sync. motor permanently excited (special applications)
P100 = ?
Enter the type of open-loop/closed-loop control
0: v/f control + speed control
1: v/f control
2: v/f control textile
3: Speed control without tachometer (f control)
4: Speed control with tachometer (n control)
5: Torque control (M control)
Note: For motor ratings over approx. 200 kW one of the
vector control types should be used (P100 > 2)
P095 = 10,12,13 P095=11
P101 = ?
Enter the rated motor voltage in V
as per rating plate
P102 = ?
Enter the rated motor current in A
as per rating plate
(group drives: total of all motor currents)
P103 = ?
Enter the motor magnetizing current as a % of the rated
motor current
If value is not known, set P103 = 0, the value is then
automatically calculated when you leave the drive setting
(see r119).
P104 = ?
IEC motor: Cos (phi)
as per rating plate
NEMA motor: nominal rating [Hp]
(group drives: total of all ratings)
P105 = ?
NEMA motor: Enter the motor efficiency in %
as per rating plate
P106 = ?
P107 = ?
Enter the rated motor frequency in Hz
as per rating plate