Operating instructions

Parameterizing steps Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
9-40 Operating Instructions SIMOVERT MASTERDRIVES
P108 = ?
Enter the rated motor speed in rpm
as per rating plate
P109 = ?
Enter the motor pole pair number
(is automatically calculated if P107 and P108 are changed)
P113 = 1
Enter the rated motor torque in Nm
as per rating plate or motor catalog (is only used for normalizing
the process data and visualization parameters)
P114 = ?
Calculate motor model "Automatic parameterization"
P115 = 1
P100 = 0,1,2
P100 = 3,4,5
Process-related conditions for closed-loop control
0: Drive for standard applications (e.g. pumps)
1: Drive with strong torsion, gear play, large moments of
inertia (e.g. paper machine)
2: Drive for very dynamic accelerations
(without load moments) (e.g. shears)
3: Drive for strong shock stressing (e.g. roll drive)
4: Drive with high smooth running characteristics at low speeds.
5: Drives with modest response requirements, which can be
optimized in their efficiency with frequent part-load operation.
6: Drive with high starting moments.
Select the motor encoder
10: Without motor encoder
11: Pulse encoder
12: Pulse encoder with control track
13: Analog input 1
14: Analog input 2
15: Pulse encoder with zero track
16: Pulse encoder with zero and control track
P130 = ?
P151 = ?
Enter the pulse number/revolution of the pulse encoder
P130 =
10,13,14
P130 =
11,12,15,16
P100 =
0,1,2
P330 = ?
Characteristic
0: Linear characteristic (constant torque drives)
1: Parabolic characteristic (fans/pumps)
P339 = ?
Release the edge modulation systems (FLM)
0: All systems
1: Edge modulation systems from 60 Hz
2: Edge modulation systems from 100 Hz
3: No edge modulation systems
4: Overmodulated space vector modulation