11-8 Operating Instructions SIMOVERT MASTERDRIVES
Fault
number
Fault Counter-measure
F059
Parameter error after factory
setting/initialization
The number of the inconsistent parameter is
indicated in fault value r949. Correct this
parameter (ALL indices) and power down and
power up the voltage again. Depending on
circumstances, several parameters may be
concerned, i.e. repeat the procedure.
F060 MLFB is missing
This is set if the MLFB = 0 after exiting
INITIALIZATION (0.0 kW). MLFB = order
number.
After acknowledgement, in INITIALIZATION
enter a suitable MLFB in parameter P070
MLFB (6SE70..). (Only possible with the
corresponding access stages to both access
parameters).
F061 Incorrect parameterization
A parameter entered during drive setting (e.g.
P107 Mot Rtd Freq, P108 Mot Rtd Speed,
P340 Pulse Frequency) is not in a
permissible range (depending on control
type)
Acknowledge the fault and change the
corresponding parameter value. The missing
parameter is indicated in r949 as a fault
value.