Operating instructions

Vector Control Chassis Type Frequency Converter Technical Data
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 4-7
Designation Value
Order No. 6SE70... 32-0FG60 32-3FG60 33-0FK60 33-5FK60 34-5FK60
Rated voltage [V]
Input
Output
3 AC 500 (- 15 %) to 600 (+ 10 %)
3 AC 0 to rated input voltage
Rated frequency [Hz]
Input
Output: V/f = constant
V = constant
50 / 60 ± 6 %
0 to 600
8 to 300
Rated current [A]
Input
Output
211
192
248
225
327
297
400
354
497
452
DC link voltage [V] 675 to 810 (± 15 %)
Rated output [kVA] 167 to 199 195 to 233 258 to 308 307 to 367 392 to 469
Auxiliary power supply [V] DC 24 (20 - 30)
Max. aux.-curr. requirement[A]
Standard version at 20 V
2.3 3.1
Max. aux.-curr. requirement[A]
Max. version at 20 V
3.5 4.3
Pulse frequency [kHz] 1.7 to 6 1.7 to 6 1.7 to 3 1.7 to 3 1.7 to 2.5
Derating curve (see Fig.4-1) ÷÷øøù
Load class II to EN 60 146-1-1
Base load current [A] 0.91 x rated output current
Base load duration [s] 240
Overload current [A] 1.36 x rated output current
Overload duration [s] 60
Load class II to EN 60 146-1-1 (additional)
Base load current [A] 0.91 x output current not additional
Base load duration [s] 270 not additional
Overload current [A] 1.6 x output current not additional
Overload duration [s] 30 not additional
Losses, cooling, power factor
Power factor
Line cosϕ1N
Converter cosϕU
0.98
< 0.92 ind.
Efficiency η (rated operation) 0.98 0.97 0.98
Power loss (at 2.5 kHz) [kW] 3.4 4.05 5.80 6.80 8.30
Cooling-air requirement [m³/s] 0.41 0.41 0.46 0.46 0.46
Sound-pressure levels, types of construction, dimensions, weights
Sound-pressure level
IP00 [dB(A)] 82 82 77 77 77
Type of construction G G K K K
Dimensions [mm]
Width
Height
Depth
508
1450
450
508
1450
450
800
1750
551
800
1750
551
800
1750
551
Weight approx. [kg] 155 155 400 400 400
Table 4-5 Air-cooled converter (part 4)