Operating instructions

Parameterization Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
8-8 Operating Instructions SIMOVERT MASTERDRIVES
Some parameters may also be displayed without a parameter number,
e.g. during quick parameterization or if "Fixed setting" is selected. In
this case, parameterization is carried out via various sub-menus.
Example of how to proceed for a parameter reset.
P
0.0 A 0 V 00
# 0.00 min-1
* 0.00
min-1
Ready
P
VectorControl
*Menu selection
OP: Upread
OP: Download
Menu Selection
*User Param.
Param Menu..
Fixed Set...
Menu Selection
*User Param.
Param Menu..
#Fixed Set...
2 x
P
Fixed Setting
*Select FactSet
FactSet.
P
Fixed Setting
*Select FactSet
#FactSet.
Fixed Setting
FactSet.
*No FactSet
Factory Setting
#FactSet.
*No FactSet
Selection of factory setting
P
Factory Setting
#FactSet.
*No FactSet
busy............
Menu Selection
*User Param..
Param. Menuü..
FixedSet...
wait
Start of factory setting
It is not possible to start the parameter reset in the "Run" status.
8.3 Parameterizing by download
The OP1S operator control panel is capable of upreading parameter
sets from the units and storing them. These parameter sets can then be
transferred to other units by download. Downloading with the OP1S is
thus the preferred method of parameterizing replacement units in a
service case.
During downloading with the OP1S, it is assumed that the units are in
the as-delivered state. The parameters for power section definition are
thus not transferred. (Refer to Section "Detailed parameterization,
power section definition")
NOTE
Downloading with
the OP1S