Operating instructions

Parameterizing steps Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
9-8 Operating Instructions SIMOVERT MASTERDRIVES
The OP1S operator control panel is capable of upreading parameter
sets from the units and storing them. These parameter sets can then be
transferred to other units by download. Downloading with the OP1S is
thus the preferred method of parameterizing replacement units in a
service case.
During downloading with the OP1S, it is assumed that the units are in
the as-delivered state. The parameters for power section definition are
thus not transferred. (Refer to Section "Detailed parameterization,
power section definition")
Parameter number Parameter name
P060 Menu selection
P070 Order No. 6SE70..
P072 Rtd Drive Amps(n)
P073 Rtd Drive Power(n)
Table 9-3 Parameters you cannot overwrite during download
The OP1S operator control panel also stores and transfers parameters
for configuring the USS interface (P700 to P704). Depending on the
parameterization of the unit from which the parameter set was originally
upread, communication between the OP1S and the unit can be
interrupted on account of changed interface parameters after
downloading has been completed. To enable communication to re-
commence, briefly interrupt the connection between the OP1S and the
unit (disconnect OP1S or the cable). The OP1S is then newly initialized
and adjusts itself after a short time to the changed parameterization via
the stored search algorithm.
By using the SIMOVIS PC program, you can upread parameter sets
from the units, store them on the hard disk or on floppy disks and
transfer them back to the units by download. You have the additional
possibility of editing the parameters off-line and of creating parameter
files especially for your application. These files do not have to contain
the complete parameter scope. They can be limited to parameters
which are relevant for the particular application.
Downloading with
the OP1S
Download with
SIMOVIS