Operating instructions

Vector Control Chassis Type Frequency Converter Parameterizing steps
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 9-11
Input unit line voltage in V
AC units: r.m.s. alternating voltage
DC units: DC link voltage
The input is important, e.g. for voltage limitation control
(Vdmax control, P515 = 1)
P060 = 3
Select "Drive setting" menu
Menu selection "Quick parameterization"
P071 = ?
P095 = ?
Enter the motor type
10: Async. IEC (international standard)
11: Async. NEMA (US standard)
P100 = ?
Enter the open/closed-loop control type (sheet r0...r5)
0: v/f open-loop control + n-controller with pulse encoder
(P130 = 11)
1: v/f open-loop control
2: v/f open-loop control, textile
3: Vector control without tachometer (f-control)
4: Vector control with tachometer (n-speed)
with pulse encoder (P130 = 11)
5: Torque control (M control)
with pulse encoder (P130 = 11)
P095 = 10 P095=11
For v/f control (0..2), a linear curve will be set in P330
(P330 = 1: parabolic).
The pulse encoder has a pulse number of P151 = 1024 per
revolution.
The following inputs of motor data are necessary if the motor deviates
from the converter data, if one of the vector control types
(P100 = 3, 4, 5) has been selected, or if speed feedback is used
(P100 = 0). In the case of motor outputs higher than approx. 200 kW,
one of the vector control types should be used.
P101 = ?
Enter the rated motor voltage in V
as per rating plate
P102 = ?
Enter the rated motor current in A
as per rating plate
(group drives: total of all motor currents)
P104 = ?
IEC motor: Cos (phi)
as per rating plate
NEMA motor: nominal rating [Hp]
(group drives: total of all ratings)
P105 = ?
Enter the motor efficiency in %
as per rating plate
P106 = ?
P107 = ?
Enter the rated motor frequency in Hz
as per rating plate