Parameterizing steps Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
9-12 Operating Instructions SIMOVERT MASTERDRIVES
P108 = ?
Enter the rated motor speed in rpm
as per rating plate
P109 = ?
Enter the motor pole pair number
(is automatically calculated)
P114 = ?
Only for vector control:
Process-related boundary conditions for control
0: Standard drives (default)
1: Torsion, gear play
2: Acceleration drives
3: Load surge
4: Smooth running characteristics
5: Efficiency optimization
6: Heavy-duty starting
See section "Drive setting"
Thermal motor protection
desired?
System with motor protection according to UL regulation?
The motor temperature is calculated via the motor current.
(In the pre-setting, motor overload protection in accordance with
UL regulation is activated!)
no yes
P382 = ?
P383 = ?
Specify motor cooling
0: self-ventilated
1: forced-ventilated
Enter the thermal time constant of the motor in s
The values can be taken from the table on the next page.
The motor load limit (P384.2) is pre-assigned to 100 %.
P383 = 0
P700.01 = ?
Select setpoint and command source (sheet s0...s4, s7)
0: PMU + MOP
1: Analog and digital inputs on the terminal strip
2: Fixed setpoints and digital inputs on the terminal strip
3: MOP and digital inputs on the terminal strip
4: USS1 (e.g. with SIMATIC)
5: SIMOLINK (SLB) (without fig.)
6: PROFIBUS (CBP) (without fig.)
7: OP1S and fixed setpoints via SCom1 (X300: PMU)
P368 = ?
Enter the USS bus address
P740 = ?
P918.01 = ?
Enter the SIMOLINK module address
Enter the PROFIBUS address
P368 = 0,1,2,3 4,7 5 6
P370 = 1
Start of quick parameterization
0: No parameter change
1: Parameter change in accordance with selected
combination of parameter modules
(automatic factory setting according to P366 = 0)
P060 = 0
Return to the user menu
End of quick parameterization