Installation manual

Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 89
OUTPUTS DEFINITIONS
Segment
2
:
INH1
(Front Door Inhibition) (S ELEC).
This shows us the state of INH1 output which depends on the option SHTCS (CS Bridge)
address 63 segment 6.
Segment 2 is on when INH1 output is activated and gives 0 V.
Segment 2 is off in the reverse case.
Segment
1
:
FE2
(Rear Door Close Signal Output) (S CONT).
This shows us the state of the Rear Door Close Signal Output (FE2).
Segment 1 is on if the Rear Door Close Signal Output is fed.
Segment 1 is off in the reverse case.
Segment
0
:
OU2
(Rear Door Open Signal Output) (S CONT).
This shows us the state of the Rear Door Open Signal Output (OU2).
Segment 0 is on if the Rear Door Open Signal Output is fed.
Segment 0 is off in the reverse case.
Ram Address
15
:
best displayed in segment mode.
Segment
7
:
DEF
(Fault Light) (S ELEC).
This shows us the state of the Fault Light Output. (DEF).
Segment 7 is on when the Fault Output is activated and gives out 0 V.
Segment 7 is off when the Fault Output is de-activated and gives out 24V.
Segment
6
:
GONG
(GONG) (S ELEC).
This shows us the state of the GONG Output (GONG).
Segment 6 is on when the Gong Output is activated and gives out 24 Volts.
Segment 6 is off when the Gong Output is de-activated and gives out 0 Volts.
Segment
5
:
FD
(Down Arrow) (S ELEC).
This shows us the state of the Down Arrow (FD).
Segment 5 is on when the FD Output is activated and gives out 24 Volts.
Segment 5 is off when the FD Output is de-activated and gives out 0 Volts.
Segment
4
:
FM
(Up Arrow) (S ELEC).
This shows us the state of the Up Arrow (FM).
Segment 4 is on when the FM Output is activated and gives out 24 Volts.
Segment 4 is off when the FM Output is de-activated and gives out 0 Volts.