User Manual
Table Of Contents
- Contents
- Safety information
- Note Ex area
- Quick start
- Quick start with the PC
- Quick start with adjustment module MINICOM
- 1 Product description
- 1.1 Function
- 1.2 Application features
- 1.3 Adjustment
- 1.4 Antennas
- 2 Types and versions
- 2.1 Survey
- 2.2 Configuration of measuring systems
- 3 Technical data
- 3.1 Technical data
- 3.2 Approvals
- 3.3 Dimensions
- 4 Mounting and installation
- 4.1 General installation instructions
- 4.2 Measurement of liquids
- 4.3 Measurement in standpipe (surge or bypass tube)
- 4.4 False echoes
- 4.5 Common installation mistakes
- 5 Electrical connection
- 5.1 Connection and connection cable
- 5.2 Connection of the sensor
- 5.3 Connection of the external indicating instrument VEGADIS 50
- 6 Setup
- 6.1 Adjustment methods
- 6.2 Adjustment with PC
- 6.3 Adjustment with adjustment module MINICOM
- 6.4 Adjustment with HART® handheld
- 7.2 Error codes
- 7 Diagnostics
- 7.1 Simulation
VEGAPULS 42 and 44 – 4 … 20 mA 85
Setup
1.1.3
1.1.2
1.3.1
1.3.2
1.3.4
1.3.6
6 Write protect None
7 Descriptor
8 Message
9 PV Sensr s/n
Final asmbly num
Revision #’s
1.3.4.2
1.3.4.3
1.3.4.4
1.3.4.5
1.3.4.7
1.3.4.8
1.3.4.9
1.3.4.10
1.3.4.11
1.3.4.1
see next
page
1.3.4.6
C
1.2.2
Switch off
control
Individual current values for test
purposes (measured value simula-
tion).
See also menu window 1.4.3.1.
on the next page
The following menu windows are not
supported by the sensor. Saving of adjust-
ments carried out here is not possible.
The adjustment of actual "empty“ or "full“
measured values should be carried out in
the menu window 4.1 and 4.2. Enter there
the meas. distance with empty vessel as
zero and the meas. distance with full
vessel as end.
Sensor serial number
E
1.4.3
1.4.3.2
OFF: Sensor signals measured values only on request
ON: Sensor signals measured values unrequested
1.4.3.2
D
like menu 1.3.1
see next
page
1.4.3.1
Multidrop operation (sensor address):
The sensor outputs beside the 4 … 20 mA
signal also a digital (HART
®
) level signal:
• Enquiry address zero, the sensor
consumes a level dependent 4 … 20 mA
current and delivers a digital (HART
®
)
level signal.
• Enquiry address 1 … 15, the sensor
delivers a digital (HART
®
) level signal
and the sensor current is frozen to 4 mA
(power supply).
The 4 … 20 mA signal is no longer
available.
Generic: SENSOR
PV
2.281 m
HELP EXIT
Generic: SENSOR
A01
8.264 mA
HELP EXIT
Generic: SENSOR
PV % rnge
45.390 %
HELP EXIT
Generic: SENSOR
PV Damp
0.000 s
0.000 s
HELP DEL ESC ENTER
Generic: SENSOR
Device information
1 Distributor
2 Model
3 Dev id
4Tag
5 Date 01/01/97
HELP SAVE HOME
Generic: SENSOR
PV Snsr unit
m
m
bbl
in
cm
ESC ENTER
Generic: SENSOR
Tag
SENSOR
SENSOR
HELP DEL ESC ENTER
Generic: SENSOR
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End
ABORT ENTER
Generic: SENSOR
Output condition
1 Analog output
2 HART output
SAVE HOME
Generic: SENSOR
HART output
1 Poll addr 0
2 Num req preams 0
3 Burst mode
4 Burst option
HELP SAVE HOME
Generic: SENSOR
Poll addr
0
0
HELP DEL ESC ENTER