86 VEGAPULS 42 and 44 4 20 mA
Setup
Continuation HART
®
menu schematic VEGAPULS 42 and 44
1.3.4.8
available initialisation words:
..SOL Meas. conditions solid
..LIQ Meas. condition liquid
..FED Delete false echo storage
..FEN04.58M False echo, e.g. at 4.58 m create new
..FEN48.67FT False echo, e.g. at 48.67 ft create new
..FEU03.68M Extend false echo storage:
add a new false echo to the false echo storage at 3.68 m
..FEU36.05FT add a new false echo to the false echo storage at 36.05 ft
initialisation word
(last entered)
Newly entered initialisation
word to be enquired with
ENTER and SEND
D
Note:
After entering the initialisation word, press "ENTER and then
"SEND.
Confirm the message to change over to manual operation with
"OK and the message to switch over to automatic operation again
with "OK.
Only then is the adjustment written into the sensor and made
active.
1.4.3.1
1.4.3.1.2
Low: In case of failure current output
goes to 22 mA
High: In case of failure current output
goes to < 3.6 mA
1.4.3.1.3
1.4.3.1.3.1
Warning:
Switch off
control!
False echo storage
Normally this menu is only
required for process vessels and
difficult installation conditions
of 1.3.4
of
1.4.3.
Generic: SENSOR
Message
..SOL
..FEN04.58M
HELP DEL ESC ENTER
Generic: SENSOR
Analog output
1 A01 13,467mA
2 A0 Alrm typ
3 Loop test
4 D/A trim
5 Scaled D/A trim
HELP SAVE HOME
Generic: SENSOR
Choose analog output
level
14 mA
2 20 mA
3 Other
4 End
Abort Enter
Generic: SENSOR
Fld dev output is
fixed at 4.000 mA
ABORT OK
Generic: SENSOR
A0 Alrm typ
Hold last out valu
Exit