User Manual

Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.
Apart from the medium also the vessel form can
inuence the measurement. To adapt the sensor to
these conditions, this menu item oers (depending on
either liquid or solid is selected) dierent options. For
Liquid these are Storage tank, Stilling tube, Open vessel
or Stirred vessel, for Solid Silo or Bunker.
Vessel form
Silo
Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.
To suppress uctuation in the measured value display,
e.g. by agitated product surfaces, an integration time
can be set. This time can be between 0 and 999
seconds. Please note that the reaction time of the entire
measurement will be longer and the sensor will react to
quick changes of the measured value with a corre-
sponding delay. In general, a time of a few seconds is
sucient to smooth the measured value display.
Damping
0 s
Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.
A linearization is necessary for all vessels in which the
vessel volume does not increase linearly with the level -
e.g. in a cylindrical or spherical tank - and the indication
or output of the volume is requested. Corresponding
linearization curves are preprogrammed for these
vessels. They represent the correlation between the
level percentage and vessel volume. By activating the
Vessel form
Damping
Linearization curve
VEGAPULS 68 - 4 ... 20 mA/HART 37
Setup with the indicating and adjustment module PLICSCOM
29261-EN-050202