appropriate curve, the volume percentage of the vessel
is displayed correctly. If the volume should not be
displayed in percent but e.g. in l or kg, a scaling can be
set in the menu item Display.
Linearization curve
linear
Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.
In this menu item you can enter an unambiguous
designation for the sensor, e.g. the measurement loop
name or the tank or product designation. In digital
systems and in the documentation of larger plants, a
unique designation should be entered for exact identi-
cation of individual measuring sites.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is nished
and you can now jump to the main menu with the [ESC]
key.
High sockets or vessel installations, such as e.g. struts
or agitators as well as buildup and weld joints on the
vessel walls cause false reections which inuence the
measurement. A false echo storage detects and marks
these false echoes so that they are no longer taken into
account for the level measurement. A false echo
memory should be created with empty vessel so that all
probably existing false reections can be detected.
False echo storage
Change?
Proceed as follows:
Sensor-TAG
False echo storage