User Manual

1 Move from the measured value display to the main
menu by pushing [OK].
2 Select the menu item Service with [–>] and conrm
with [OK]. Now the menu item false echo storage is
displayed.
3 Conrm False echo storage - Change now with [OK]
and select in the below menu Create new. Enter the
actual distance from the sensor to the product
surface. All false echoes in this area are detected by
the sensor and saved after conrming with [OK].
Note:
Check the distance to the product surface as in case of
awrong(too big) setting, the real level will be saved as
false echo. Hence the level can no longer be detected in
this area.
Additional adjustment and diagnosis options such as e.
g. scaling, simulation or trend curve presentation are
shown in the following menu schematic. Y ou will nd a
detailed description of these menu items in the operating
instructions manual of the indicating and adjustment
module PLICSCOM.
Optional settings
VEGAPULS 68 - 4 ... 20 mA/HART 39
Setup with the indicating and adjustment module PLICSCOM