Operating Instructions

Table Of Contents
12
4 Mounting
VEGAPULS C 21 • Two-wire 4 … 20 mA/HART
58341-EN-191014
The position of the polarisation is in the middle of the type label on the
instrument.
1
Fig. 6: Position of the polarisation
1 Middle of the type label
When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) from the vessel wall. If the sensor is installed in the center
of dished or round vessel tops, multiple echoes can arise. However,
these can be suppressed by an appropriate adjustment (see chapter
"Setup").
If you cannot maintain this distance, you should carry out a false
signal suppression during setup. This applies particularly if buildup on
the vessel wall is expected. In such cases, we recommend repeating
the false signal suppression at a later date with existing buildup.
> 200 mm
(7.87
")
Fig. 7: Mounting of the radar sensor on round vessel tops
In vessels with conical bottom it can be advantageous to mount the
sensor in the centre of the vessel, as measurement is then possible
down to the bottom.
Fig. 8: Mounting of the radar sensor on vessels with conical bottom
Installation position