User's Manual

Level Switching status Signal lamp - Re-
lay (yellow)
Mode min.
Dry run protection
53 4
(8)(6) (7)
Relay deenergized
Failure of the supply
voltage
(max./min. mode)
any
53 4
(8)(6) (7)
Relay deenergized
Failure any
53 4
(8)(6) (7)
Relay deenergized Red failure LED
lights
Depending on the switching function your relay output should carry
out, you can determine the switching direction by means of the slide
switch.
l For max. indication or overll protection set the slide sw itch to
position max.
l For min. indication or dry run protection, set the slide switch to
position min.
The relay is energized if the yellow relay control lamp lights.
With the two keys you can change the LED indication strip and adjust
the switching point to the medium.
The keys are lowered to avoid unintentional changes of the setting. For
adjustment, use for example, a small screwdriver.
If you press one of the keys for more than two seconds, the adjustment
range shifts automatically in the respective direction. The greater the
distance between emitting and receiving unit, the greater the adjust-
ment range of the indication. The LED indication strip always shows a
small sec tion of the actual measuring range.
Pressing the "<--" key makes the sensor more sensitive. Pressing the
"-->" key makes the sensor less sensitive.
Sensitivity adjustment
24 VEGAMIP R61 - Relay
6 Setup
35786-EN-100531